The 3AXD50000417728: Normal-use output is 15 kW at 60 A — that's the continuous rating for typical HVAC fan and pump loads. Light-overload use is 15.0 kW at 59 A, essentially matching normal use but with a slightly lower current limit for cyclic loads. Standby loss is 15 W, and power consumption at rated load is 781 W. Efficiency class IE2. The drive is rated for 24 kV·A apparent output power.
Wall-mounted, IP21, NEMA Type 1. Maximum ambient 40 °C, altitude 1000 m without derating. Humidity up to 95% RH. Sound level 76 dB(A) — noticeable in a quiet mechanical room, but typical for this frame class. Input frequency range 47.5–63 Hz, so it handles weak utility or generator supply. The drive includes a control unit and a lithium coin cell (CR2032, 220 mAh) for real-time clock backup.
Two analog inputs, two analog outputs. Six digital inputs and three digital outputs. No onboard industrial Ethernet port — BACnet is the primary fieldbus, which is standard for HVAC building management integration.