Skip to main content
ABB 3AXD50000417742 — AC Drive (VFD) 240V

ABB 3AXD50000417742 ACH580-01 HVAC Drive, 30 kW, 115 A, 230

MPN3AXD50000417742
Active

ABB ACH580-01 series, LV AC wall-mounted HVAC drive, 30 kW / 115 A normal duty, 22 kW / 88 A heavy duty, 200-240 V 3-phase, IP21, BACnet, frame R5.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Electrical Output

3AXD50000417742 — Electrical Output
ParameterValue
Output power, normal duty (Pn)30 kW
Output current, normal duty (In)115 A
Output power, heavy duty (PhD)22.0 kW
Output current, heavy duty (IhD)88 A
Output power, light-overload duty (PlD)30 kW
Output current, light-overload duty (IlD)114 A
Apparent power output46 kV·A
Efficiency class (IE)IE2
Standby loss19 W
Power consumption1285 W

Electrical Input

3AXD50000417742 — Electrical Input
ParameterValue
Input voltage range200 ... 240 V
Number of phases3-phase
Frequency47.5 ... 63 Hz

Control & I/O

3AXD50000417742 — Control & I/O
ParameterValue
Digital inputs / outputs6 / 3
Communication protocolBACNET
Analog inputs2
Analog outputs2
Hardware interfacesIndustrial Ethernet 0

Environmental

3AXD50000417742 — Environmental
ParameterValue
Temperature rating, max.Maximum 40 °C
Operating humidity95
Altitude1000 m
Noise level63 dB(A)

Mechanical

3AXD50000417742 — Mechanical
ParameterValue
Degree of protection (IP)IP21
Enclosure type (NEMA)Type1
Frame sizeR5
Mounting typeWall-mounted

Approvals

3AXD50000417742 — Approvals
ParameterValue
RoHS complianceFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
REACH complianceTrue - contains substances > 0.1 mass percentage

Product details

The ABB 3AXD50000417742 is the order code for an ACH580-01-115A-2, a wall-mounted LV AC drive built for HVAC applications. Rated 30 kW / 115 A in normal (light-overload) duty and 22 kW / 88 A in heavy-duty use, on a 200-240 V 3-phase supply. Frame size R5, IP21, NEMA Type 1 enclosure — goes on a wall, not inside a panel.

Normal-duty output current is 115 A (114 A light-overload), heavy-duty is 88 A. The apparent power output is 46 kV·A. Standby loss is 19 W; full-load power consumption is 1285 W. Efficiency class IE2. Ambient temperature max 40 °C, altitude 1000 m without derating. Operating humidity up to 95% RH. Built-in BACnet communication — no extra gateway needed for BMS integration. Two analog inputs, two analog outputs, six digital inputs, three digital outputs. That covers the typical AHU or chiller I/O map without an expansion module.

Frequently asked questions

What compliance documentation does this drive carry?

RoHS compliant per EU Directive 2011/65/EU and Amendment 2015/863. REACH registered (contains substances > 0.1 mass percentage). SCIP number 78feb6f4-2343-45e6-a509-fef3119deda6 Finland. WEEE category 4.

What is the SCIP number for this drive?

SCIP 78feb6f4-2343-45e6-a509-fef3119deda6 Finland.

MPN
3AXD50000417742