The ABB 3AXD50000417742 is the order code for an ACH580-01-115A-2, a wall-mounted LV AC drive built for HVAC applications. Rated 30 kW / 115 A in normal (light-overload) duty and 22 kW / 88 A in heavy-duty use, on a 200-240 V 3-phase supply. Frame size R5, IP21, NEMA Type 1 enclosure — goes on a wall, not inside a panel.
Normal-duty output current is 115 A (114 A light-overload), heavy-duty is 88 A. The apparent power output is 46 kV·A. Standby loss is 19 W; full-load power consumption is 1285 W. Efficiency class IE2. Ambient temperature max 40 °C, altitude 1000 m without derating. Operating humidity up to 95% RH. Built-in BACnet communication — no extra gateway needed for BMS integration. Two analog inputs, two analog outputs, six digital inputs, three digital outputs. That covers the typical AHU or chiller I/O map without an expansion module.