Skip to main content
ABB 3AXD50000417766 — AC Drive (VFD) 240V

ABB 3AXD50000417766 ACH580-01 Drive, 45 kW, 171 A, 230 V

MPN3AXD50000417766
Active

ABB ACH580-01 series, LV AC wall-mounted drive for HVAC, 3AXD50000417766, 45 kW normal-use output, 171 A, 230 V input, IP21, BACnet.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Electrical Output

3AXD50000417766 — Electrical Output
ParameterValue
Output power, normal duty (Pn)45 kW
Output current, normal duty (In)171 A
Output power, heavy duty (PhD)37 kW
Output current, heavy duty (IhD)143 A
Output power, light-overload duty (PlD)45 kW
Output current, light-overload duty (IlD)169 A
Apparent power output68 kV·A
Efficiency class (IE)IE2
Standby loss22 W
Power consumption2000 W

Electrical Input

3AXD50000417766 — Electrical Input
ParameterValue
Input voltage range200 ... 240 V
Number of phases3-phase
Frequency47.5 ... 63 Hz

Control & I/O

3AXD50000417766 — Control & I/O
ParameterValue
Digital inputs / outputs6 / 3
Communication protocolBACNET
Analog inputs2
Analog outputs2
Hardware interfacesIndustrial Ethernet 0

Environmental

3AXD50000417766 — Environmental
ParameterValue
Temperature rating, max.Maximum 40 °C
Operating humidity95
Altitude1000 m
Noise level67 dB(A)

Mechanical

3AXD50000417766 — Mechanical
ParameterValue
Degree of protection (IP)IP21
Enclosure type (NEMA)Type1
Frame sizeR7
Mounting typeWall-mounted

Approvals

3AXD50000417766 — Approvals
ParameterValue
RoHS complianceFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
REACH complianceTrue - contains substances > 0.1 mass percentage

Product details

It delivers 45 kW output at 171 A under normal use, with a heavy-duty rating of 37 kW at 143 A. Input is 200–240 V three-phase, 47.5–63 Hz. The drive includes the control unit and comes in frame size R7, wall-mounted, with IP21 protection and NEMA Type 1 enclosure.

Normal-use output current of 171 A (light-overload, 45 kW) is the number to size branch protection and cabling against. Standby loss is 22 W, so the drive idles cool in a panel. Sound level is 67 dB(A) — noticeable in a quiet mechanical room but typical for an R7 frame at full fan speed.

Communications and I/O

BACnet is on board as standard — no extra option card needed for BMS integration. Two analog inputs and two analog outputs are available for feedback and setpoint signals. Six digital inputs and three digital outputs handle start/stop, fault reset, and status indication. No onboard industrial Ethernet interface; if you need Modbus TCP or PROFINET, plan for an external gateway or option module.

Frequently asked questions

What is the SCIP number for this drive?

The SCIP number is cdfd6c1b-d797-41db-b2a0-2e3d5e5a1071, registered in Finland.

What compliance documentation is available?

RoHS compliance per EU Directive 2011/65/EU and Amendment 2015/863 (date 20240508). REACH declaration confirms substances above 0.1% mass (date 20250905).

What are the key output ratings?

Normal-use (light-overload) output is 45 kW at 171 A; heavy-duty use is 37 kW at 143 A. Input is 200–240 V three-phase.

MPN
3AXD50000417766