Skip to main content
ABB 3AXD50000417780 — AC Drive (VFD) 240V

ABB 3AXD50000417780 ACH580-01 Drive, 75 kW, 276 A, 230 V

MPN3AXD50000417780
Active

ABB ACH580-01 series, LV AC wall-mounted drive for HVAC, 3AXD50000417780, 75 kW / 276 A normal duty, 230 V 3-phase input, frame size R8.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Electrical Output

3AXD50000417780 — Electrical Output
ParameterValue
Output power, normal duty (Pn)75 kW
Output current, normal duty (In)276 A
Output power, heavy duty (PhD)55 kW
Output current, heavy duty (IhD)211 A
Output power, light-overload duty (PlD)75 kW
Output current, light-overload duty (IlD)273 A
Apparent power output110 kV·A
Efficiency class (IE)IE2
Standby loss26 W
Power consumption3571 W

Electrical Input

3AXD50000417780 — Electrical Input
ParameterValue
Input voltage range200 ... 240 V
Number of phases3-phase
Frequency47.5 ... 63 Hz

Control & I/O

3AXD50000417780 — Control & I/O
ParameterValue
Digital inputs / outputs6 / 3
Communication protocolBACNET
Analog inputs2
Analog outputs2
Hardware interfacesIndustrial Ethernet 0

Environmental

3AXD50000417780 — Environmental
ParameterValue
Temperature rating, max.Maximum 40 °C
Operating humidity95
Altitude1000 m
Noise level65 dB(A)

Mechanical

3AXD50000417780 — Mechanical
ParameterValue
Degree of protection (IP)IP21
Enclosure type (NEMA)Type1
Frame sizeR8
Mounting typeWall-mounted

Approvals

3AXD50000417780 — Approvals
ParameterValue
RoHS complianceFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
REACH complianceTrue - contains substances > 0.1 mass percentage

Product details

The 3AXD50000417780: Rated for a maximum ambient of 40 °C and altitude up to 1000 m without derating. IP21 enclosure with NEMA Type 1 keeps it suited for indoor installation, not washdown environments. Communication is BACnet out of the box — no option card needed for BAS integration. Onboard analog I/O: 2 inputs and 2 outputs. Digital I/O counts 6 inputs and 3 outputs.

Three duty classes are defined: light-overload (75 kW / 273 A), normal-use (75 kW / 276 A), and heavy-duty (55 kW / 211 A). Standby loss is 26 W — relevant for energy code compliance when the drive is idle but powered. Efficiency class IE2.

Wall-mounted, frame size R8. Sound level 65 dB(A) — noticeable in a mechanical room but not intrusive. Operating humidity up to 95% RH (non-condensing). Contains a CR2032 lithium coin cell (220 mAh, 3 V) for real-time clock backup. The SCIP number is c68079d0-d1d5-4fa0-b4a7-6e12fd5d3c68 Finland.

Frequently asked questions

What is the SCIP number for this drive?

The SCIP number is c68079d0-d1d5-4fa0-b4a7-6e12fd5d3c68 Finland.

What compliance documentation does ABB provide for 3AXD50000417780?

RoHS compliance per EU Directive 2011/65/EU and Amendment 2015/863 (declared 20240508). REACH declaration confirms substances above 0.1% mass (declared 20250905).

What are the normal-duty and heavy-duty current ratings?

Normal-duty output current is 276 A (75 kW); heavy-duty output current is 211 A (55 kW). Light-overload rating is 273 A (75 kW).

What communication protocol does this drive support?

BACnet is the onboard protocol, standard for building automation integration.

MPN