Skip to main content
ABB 3AXD50000417841 — AC Drive (VFD) 240V

ABB 3AXD50000417841 ACH580 HVAC Drive, 5.5 kW, 24.5 A

MPN3AXD50000417841
Active

ABB ACH580-01-025A-2+B056, LV AC wall-mounted HVAC drive, 5.5 kW / 24.5 A normal use, 200-240 V, IP55, NEMA 12, BACnet, frame R2.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Electrical Output

3AXD50000417841 — Electrical Output
ParameterValue
Output power, normal duty (Pn)5.5 kW
Output current, normal duty (In)24.5 A
Output power, heavy duty (PhD)4.0 kW
Output current, heavy duty (IhD)16.7 A
Output power, light-overload duty (PlD)5.5 kW
Output current, light-overload duty (IlD)24.2 A
Apparent power output9.8 kV·A
Efficiency class (IE)IE2
Standby loss14 W
Power consumption255 W

Electrical Input

3AXD50000417841 — Electrical Input
ParameterValue
Input voltage range200 ... 240 V
Number of phases3-phase
Frequency47.5 ... 63 Hz

Control & I/O

3AXD50000417841 — Control & I/O
ParameterValue
Digital inputs / outputs6 / 3
Communication protocolBACNET
Analog inputs2
Analog outputs2
Hardware interfacesIndustrial Ethernet 0

Environmental

3AXD50000417841 — Environmental
ParameterValue
Temperature rating, max.Maximum 40 °C
Operating humidity95

Mechanical

3AXD50000417841 — Mechanical
ParameterValue
Degree of protection (IP)IP55
Enclosure type (NEMA)Type12
Frame sizeR2
Mounting typeWall-mounted

Approvals

3AXD50000417841 — Approvals
ParameterValue
RoHS complianceFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
REACH complianceTrue - contains substances > 0.1 mass percentage

Product details

Drive selection memo for HVAC duty

The ABB 3AXD50000417841 is a wall-mounted HVAC drive, rated 5.5 kW normal use at 24.5 A on a 200-240 V three-phase supply. Heavy-duty use drops to 4.0 kW at 16.7 A. IP55 with NEMA Type 12 enclosure suits washdown or dusty mechanical rooms; wall-mount frame R2 keeps the footprint compact. BACnet communication is onboard — no option card needed for BAS integration. The drive includes a control unit, so the BOM line is self-contained. Standby loss of 14 W matters for continuous fan operation where idle power adds up across a bank of drives.

I/O and fieldbus slice

Two analog inputs and two analog outputs handle pressure or temperature transducers; six digital inputs and three digital outputs cover start/stop, fault reset, and status feedback. No industrial Ethernet interface is present — this is a BACnet MS/TP or native BACnet drive, not a PROFINET or EtherNet/IP variant. If the BMS requires BACnet/IP, verify the controller gateway or consider the Ethernet option slot. The drive accepts 47.5-63 Hz input, so it works on 50 Hz or 60 Hz mains without reconfiguration. Efficiency is IE2 class — adequate for HVAC where part-load efficiency is more critical than full-load IE4.

Lifecycle and compliance posture

No end-of-life notification or last-time-buy window is in effect. For a BOM that needs a qualified HVAC drive with BACnet, this part is a stable line item — no requalification trigger from obsolescence.

Frequently asked questions

What compliance documentation does this drive provide?

RoHS compliance per EU Directive 2011/65/EU and Amendment 2015/863. REACH declaration confirms substances above 0.1 mass percentage are present. The SCIP number cf2353ee-9777-4c0e-a5fb-5527ed389255 (Finland) is registered for EU waste reporting.

What does the 'Includes: With control unit' mean?

The drive ships with a control unit integrated — no separate order for a control panel or keypad is needed for basic operation and parameter setup.

MPN