The 3AXD50000417865: The 47 A normal-use output current is the figure to size branch protection and cabling for continuous fan/pump duty. If your application cycles at heavy overload (e.g. high-torque start or rapid deceleration), the 30.8 A heavy-duty rating governs — stay within that for the rated overload profile. Light-overload use at 46.2 A gives a narrow margin above heavy duty but still below normal. Input voltage is 200…240 V, 3-phase, 47.5…63 Hz — confirm your line side matches before committing. Enclosure is IP55 / NEMA Type 12, wall-mounted, frame R3. That means it handles dust and hose-down in HVAC mechanical rooms or light industrial washdown areas. Ambient temperature max is 40 °C, humidity up to 95% RH. The standby loss of 15 W is low enough to ignore in most panel heat calculations.
Two analog inputs and two analog outputs are on board; six digital inputs and three digital outputs handle start/stop, fault reset, and speed reference. BACnet is the native fieldbus — no option card needed for BMS integration. No Industrial Ethernet interface is fitted; if you need Modbus TCP or PROFINET, that is a different variant.