Skip to main content
ABB 3AXD50000417902 — AC Drive (VFD) 240V

ABB 3AXD50000417902 ACH580 HVAC Drive, 37 kW, 144 A, IP55

MPN3AXD50000417902
Active

ABB ACH580-01 wall-mounted HVAC drive, 3AXD50000417902, 37 kW normal use, 144 A, 200-240 V, IP55, BACnet, frame R6.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Electrical Output

3AXD50000417902 — Electrical Output
ParameterValue
Output power, normal duty (Pn)37 kW
Output current, normal duty (In)144 A
Output power, heavy duty (PhD)30.0 kW
Output current, heavy duty (IhD)114 A
Output power, light-overload duty (PlD)37 kW
Output current, light-overload duty (IlD)143 A
Apparent power output57 kV·A
Efficiency class (IE)IE2
Standby loss22 W
Power consumption1932 W

Electrical Input

3AXD50000417902 — Electrical Input
ParameterValue
Input voltage range200 ... 240 V
Number of phases3-phase
Frequency47.5 ... 63 Hz

Control & I/O

3AXD50000417902 — Control & I/O
ParameterValue
Digital inputs / outputs6 / 3
Communication protocolBACNET
Analog inputs2
Analog outputs2
Hardware interfacesIndustrial Ethernet 0

Environmental

3AXD50000417902 — Environmental
ParameterValue
Temperature rating, max.Maximum 40 °C
Operating humidity95

Mechanical

3AXD50000417902 — Mechanical
ParameterValue
Degree of protection (IP)IP55
Enclosure type (NEMA)Type12
Frame sizeR6
Mounting typeWall-mounted

Approvals

3AXD50000417902 — Approvals
ParameterValue
RoHS complianceFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
REACH complianceTrue - contains substances > 0.1 mass percentage

Product details

The ABB 3AXD50000417902 is a wall-mounted HVAC drive rated for 37 kW normal use at 144 A on a 200-240 V three-phase supply. It ships with the control unit included and communicates over BACnet.

Normal-use output current is 144 A; heavy-duty use drops to 114 A at 30.0 kW. That spread tells you the drive is sized for a constant-torque HVAC fan or pump load — the heavy-duty figure governs if you need headroom for a variable-torque profile or a motor that occasionally overloads. Light-overload use matches the normal-use current at 143 A, so the drive doesn't force a derating for standard building loads. Standby loss is 22 W, which matters for energy-code compliance in continuously occupied mechanical rooms. The IP55 enclosure and NEMA Type12 rating mean it handles dust and hose-down cleaning without a separate cabinet — wall-mount it directly in the equipment room.

Two analog inputs and two analog outputs are on board — enough for a speed reference and feedback from a pressure or temperature transmitter. Six digital inputs and three digital outputs handle start/stop, fault reset, and status indication. There is no Industrial Ethernet port; BACnet is the only fieldbus, so if the BMS speaks BACnet MS/TP, this drive connects directly without a gateway.

Frequently asked questions

What compliance documentation is available for this drive?

RoHS compliance per EU Directive 2011/65/EU and Amendment 2015/863 (dated 20240508), REACH declaration (dated 20250905) noting substances above 0.1 mass percentage, and SCIP number 17a7c876-3c0e-4fce-930a-1904c59b53dd Finland under WEEE Category 4.

What are the key ratings for this drive?

Normal use: 37 kW, 144 A. Heavy-duty use: 30.0 kW, 114 A. Input 200-240 V three-phase, 47.5-63 Hz. IP55, NEMA Type12, IE2 efficiency. Standby loss 22 W.

Does this drive include a control unit?

Yes, the listing includes the control unit as part of the order code.

What fieldbus protocol does it support?

BACnet is the listed communication protocol. There is no Industrial Ethernet port.

MPN
3AXD50000417902