Specifications

Electrical Output

3AXD50000417919 — Electrical Output
ParameterValue
Output power, normal duty (Pn)45 kW
Output current, normal duty (In)171 A
Output power, heavy duty (PhD)37 kW
Output current, heavy duty (IhD)143 A
Output power, light-overload duty (PlD)45 kW
Output current, light-overload duty (IlD)169 A
Apparent power output68 kV·A
Efficiency class (IE)IE2
Standby loss22 W
Power consumption2000 W

Electrical Input

3AXD50000417919 — Electrical Input
ParameterValue
Input voltage range200 ... 240 V
Number of phases3-phase
Frequency47.5 ... 63 Hz

Control & I/O

3AXD50000417919 — Control & I/O
ParameterValue
Digital inputs / outputs6 / 3
Communication protocolBACNET
Analog inputs2
Analog outputs2
Hardware interfacesIndustrial Ethernet 0

Environmental

3AXD50000417919 — Environmental
ParameterValue
Temperature rating, max.Maximum 40 °C
Operating humidity95

Mechanical

3AXD50000417919 — Mechanical
ParameterValue
Degree of protection (IP)IP55
Enclosure type (NEMA)Type12
Frame sizeR7
Mounting typeWall-mounted

Approvals

3AXD50000417919 — Approvals
ParameterValue
RoHS complianceFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
REACH complianceTrue - contains substances > 0.1 mass percentage

Product details

The ABB 3AXD50000417919 is an ACH580-01 wall-mounted LV AC drive sized for a 45 kW motor on 200-240 V three-phase supply, delivering 171 A in normal use. Heavy-duty use drops to 37 kW / 143 A; light-overload use holds at 45 kW / 169 A. Frame size R7, IP55, NEMA Type12 enclosure — suitable for washdown or dusty HVAC plant rooms. BACnet on board; no Industrial Ethernet interface. Standby loss is 22 W.

Integration notes

Wall-mounted — plan for gland-plate entry at the bottom. Ambient max 40 °C; derate above that. Two analog inputs, two analog outputs; six digital inputs, three digital outputs. The control unit is included. Lithium coin cell (CR2032, 220 mAh) backs the real-time clock; expect replacement every few years. BACnet MS/TP or BACnet/IP — confirm the exact variant from the full datasheet before wiring.

Frequently asked questions

What compliance documentation is available for this drive?

RoHS compliant per EU Directive 2011/65/EU and Amendment 2015/863; REACH declaration confirms substances above 0.1 mass percentage. SCIP number dc827d29-312d-433e-afb4-0816392e0848 Finland.

What are the key output ratings for normal and heavy-duty use?

Normal use: 45 kW, 171 A. Heavy-duty use: 37 kW, 143 A. Light-overload use: 45 kW, 169 A.

MPN