Skip to main content
ABB 3AXD50000417940 — AC Drive (VFD) 240V

ABB 3AXD50000417940 ACQ580-01 drive, 0.75 kW, 4.7 A, 230 V

MPN3AXD50000417940
Active

ABB ACQ580-01 LV AC wall-mounted drive, 0.75 kW, 4.7 A, 200-240 V, IP21, NEMA 1, IE2.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Electrical Output

3AXD50000417940 — Electrical Output
ParameterValue
Output power, normal duty (Pn)0.75 kW
Output current, normal duty (In)4.7 A
Output power, heavy duty (PhD)0.55 kW
Output current, heavy duty (IhD)3.5 A
Output power, light-overload duty (PlD)0.75 kW
Output current, light-overload duty (IlD)4.6 A
Apparent power output1.9 kV·A
Efficiency class (IE)IE2
Standby loss13 W
Power consumption53 W

Electrical Input

3AXD50000417940 — Electrical Input
ParameterValue
Input voltage range200 ... 240 V
Number of phases3-phase
Frequency47.5 ... 63 Hz
Power factor0.98

Control & I/O

3AXD50000417940 — Control & I/O
ParameterValue
Digital inputs / outputs6 / 3
Communication protocolCAN
Analog inputs2
Analog outputs2
Hardware interfacesIndustrial Ethernet 0

Environmental

3AXD50000417940 — Environmental
ParameterValue
Temperature rating, max.Maximum 40 °C
Operating humidity5 ... 95
Altitude4000 m
Noise level59 dB(A)

Mechanical

3AXD50000417940 — Mechanical
ParameterValue
Degree of protection (IP)IP21
Enclosure type (NEMA)Type1
Frame sizeR1
Mounting typeWall-mounted

Approvals

3AXD50000417940 — Approvals
ParameterValue
RoHS complianceFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
REACH complianceTrue - contains substances > 0.1 mass percentage

Product details

The ABB 3AXD50000417940 is an ACQ580-01 wall-mounted drive sized for a 0.75 kW motor on a 200-240 V three-phase supply. Normal-use output current is 4.7 A; heavy-duty use drops to 3.5 A at 0.55 kW. Wall-mounted with IP21 and NEMA Type 1 enclosure — suitable for indoor clean environments, not washdown areas. Ambient temperature max 40 °C; derate above that. Efficiency class IE2.

Two analog inputs and two analog outputs are available for process signals — typical for a water/wastewater drive handling pressure or flow feedback. Six digital inputs and three digital outputs cover start/stop, fault reset, and status indication. Communication is CAN-based; no onboard industrial Ethernet, so if you need PROFINET or EtherNet/IP, plan for an option module.

Installation notes

Operating humidity 5-95% non-condensing. Standby loss 13 W; power consumption at rated load is 53 W. Sound level 59 dB(A) — quiet enough for a pump room but not silent. Power factor 0.98. Frequency range 47.5-63 Hz covers 50/60 Hz grids. Includes the control unit; battery is a CR2032 lithium coin cell (220 mAh, 3 V) for parameter backup.

Frequently asked questions

What compliance documentation is available for this drive?

RoHS compliance per EU Directive 2011/65/EU and Amendment 2015/863 (date 20240508). REACH declaration confirms substances above 0.1 mass percentage (date 20250905). SCIP number 8105d671-49fa-4c1c-836d-baf56982886a Finland is registered.

What is the altitude rating of this drive?

Rated for installation at altitudes up to 4000 m without derating.

What is the SCIP number for this product?

SCIP number 8105d671-49fa-4c1c-836d-baf56982886a Finland is registered for waste reporting compliance.

Does this drive have industrial Ethernet onboard?

No, the drive has zero industrial Ethernet interfaces. Communication is CAN-based; an option module is required for Ethernet protocols.

MPN