Skip to main content
ABB 3AXD50000418053 — AC Drive (VFD) 240V

ABB 3AXD50000418053 ACQ580-01 Drive, 37 kW, 144 A, 230 V

MPN3AXD50000418053
Active

ABB, ACQ580-01 series, LV AC wall-mounted drive, 3AXD50000418053, 37 kW / 144 A, 200–240 V, 3-phase, IP21, frame R6.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Electrical Output

3AXD50000418053 — Electrical Output
ParameterValue
Output power, normal duty (Pn)37 kW
Output current, normal duty (In)144 A
Output power, heavy duty (PhD)30 kW
Output current, heavy duty (IhD)114 A
Output power, light-overload duty (PlD)37 kW
Output current, light-overload duty (IlD)143 A
Apparent power output57 kV·A
Efficiency class (IE)IE2
Standby loss22 W
Power consumption1932 W

Electrical Input

3AXD50000418053 — Electrical Input
ParameterValue
Input voltage range200 ... 240 V
Number of phases3-phase
Frequency47.5 ... 63 Hz
Power factor0.98

Control & I/O

3AXD50000418053 — Control & I/O
ParameterValue
Digital inputs / outputs6 / 3
Communication protocolCAN
Analog inputs2
Analog outputs2
Hardware interfacesIndustrial Ethernet 0

Environmental

3AXD50000418053 — Environmental
ParameterValue
Temperature rating, max.Maximum 40 °C
Operating humidity5 ... 95
Altitude4000 m
Noise level67 dB(A)

Mechanical

3AXD50000418053 — Mechanical
ParameterValue
Degree of protection (IP)IP21
Enclosure type (NEMA)Type1
Frame sizeR6
Mounting typeWall-mounted

Approvals

3AXD50000418053 — Approvals
ParameterValue
RoHS complianceFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
REACH complianceTrue - contains substances > 0.1 mass percentage

Product details

The 3AXD50000418053: The drive carries three output current ratings that map to different duty cycles. Normal-duty (light-overload) use delivers 37 kW at 143–144 A — that's your standard pump or fan curve. The apparent power output is 57 kV·A, and the power factor sits at 0.98. Standby loss is 22 W, so it's not eating much on idle.

Wall-mounted only — no floor-stand option in this frame. Rated for a maximum ambient temperature of 40 °C, altitude up to 4000 m, and operating humidity from 5 to 95% RH. Sound level is 67 dB(A). The enclosure is IP21, so it's splash-proof but not hose-down; keep it in a clean, dry electrical room or a ventilated cabinet.

I/O and control

The drive provides 2 analog inputs and 2 analog outputs, plus 6 digital inputs and 3 digital outputs. Communication is via CAN; there are zero industrial Ethernet interfaces, so if you need Modbus TCP or PROFINET, you'll need an external gateway or a different drive variant. The control unit is included. A lithium coin cell (CR2032, 220 mAh, 3 V) backs the real-time clock.

Frequently asked questions

What are the key output ratings for normal and heavy-duty use?

Normal-duty (light-overload) output is 37 kW at 143–144 A. Heavy-duty output is 30 kW at 114 A. The apparent power output is 57 kV·A.

What is the input voltage and frequency range?

Input voltage is 200–240 V three-phase, frequency 47.5–63 Hz.

What enclosure rating and mounting type does this drive have?

IP21 / NEMA Type 1 enclosure, wall-mounted only. Frame size R6.

MPN
3AXD50000418053