It delivers 45 kW normal-use output at 171 A, with a heavy-duty rating of 37 kW at 143 A, on a 200-240 V 3-phase supply. Frame size R7, wall-mounted, IP21 / NEMA Type 1 enclosure. Runs on 47.5 to 63 Hz input frequency. Efficiency class IE2. Standby loss 22 W; power consumption at rated load is 2000 W. Apparent power output 68 kVA. Sound level 67 dB(A).
Normal use (Pn) 45 kW at 171 A. Heavy-duty use (PhD) 37 kW at 143 A. Light-overload use (PlD) 45 kW at 169 A. Input voltage 200-240 V AC, 3-phase, 47.5-63 Hz. Power factor 0.98 at rated load. Efficiency IE2.
Onboard I/O: 6 digital inputs, 3 digital outputs, 2 analog inputs, 2 analog outputs. Communication via CAN bus; no built-in Industrial Ethernet interface (0 hardware interfaces for Ethernet). For Ethernet fieldbus, you'll need an optional fieldbus adapter module.
Rated for ambient temperature up to 40 °C, altitude up to 4000 m, and relative humidity 5-95% non-condensing. IP21 / NEMA Type 1 enclosure — drip-proof, suitable for indoor panel or wall mounting in clean environments. SCIP number cdfd6c1b-d797-41db-b2a0-2e3d5e5a1071 (Finland).