Skip to main content
ABB 3AXD50000418176 — AC Drive (VFD) 240V

ABB 3AXD50000418176 ACQ580-01 Drive, 15 kW, 60 A, 230 V

MPN3AXD50000418176
Active

ABB ACQ580-01 wall-mounted drive, 15 kW normal-duty, 60 A output, 200–240 V 3-phase, IP55, frame R3.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Electrical Output

3AXD50000418176 — Electrical Output
ParameterValue
Output power, normal duty (Pn)15 kW
Output current, normal duty (In)60 A
Output power, heavy duty (PhD)11 kW
Output current, heavy duty (IhD)46.2 A
Output power, light-overload duty (PlD)15 kW
Output current, light-overload duty (IlD)59 A
Apparent power output24 kV·A
Efficiency class (IE)IE2
Standby loss15 W
Power consumption781 W

Electrical Input

3AXD50000418176 — Electrical Input
ParameterValue
Input voltage range200 ... 240 V
Number of phases3-phase
Frequency47.5 ... 63 Hz
Power factor0.98

Control & I/O

3AXD50000418176 — Control & I/O
ParameterValue
Digital inputs / outputs6 / 3
Communication protocolCAN
Analog inputs2
Analog outputs2
Hardware interfacesIndustrial Ethernet 0

Environmental

3AXD50000418176 — Environmental
ParameterValue
Temperature rating, max.Maximum 40 °C
Operating humidity5 ... 95
Altitude4000 m
Noise level76 dB(A)

Mechanical

3AXD50000418176 — Mechanical
ParameterValue
Degree of protection (IP)IP55
Enclosure type (NEMA)Type12
Frame sizeR3
Mounting typeWall-mounted

Approvals

3AXD50000418176 — Approvals
ParameterValue
RoHS complianceFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
REACH complianceTrue - contains substances > 0.1 mass percentage

Product details

The ABB 3AXD50000418176 is a wall-mounted drive for water and wastewater. It's rated for 15 kW output in normal use (60 A), with heavy-duty capability at 11 kW (46.2 A). Input is 200–240 V three-phase, and the enclosure is IP55 / NEMA 12. Rated altitude goes to 4000 m, so it handles high-altitude installations without derating — useful for pumping stations in mountainous areas. Standby loss is 15 W, and it draws 781 W at full load, which is respectable for this power class. Sound level is 76 dB(A) — not silent, but typical for a frame R3 drive running a fan.

This drive carries three duty ratings: normal-use (Pn) at 15 kW / 60 A, heavy-duty (PhD) at 11 kW / 46.2 A, and light-overload (PlD) at 15 kW / 59 A. The 60 A normal rating is for steady-running centrifugal pumps or fans where the load curve is predictable. Power factor is 0.98, so it's pretty easy on the supply side.

I/O and connectivity — what's on the van

2 analog inputs and 2 analog outputs. Digital I/O is 6 inputs and 3 outputs. Communication is CAN-based; no onboard Ethernet.

Frequently asked questions

What are the key output ratings for this drive?

Normal use: 15 kW, 60 A. Heavy-duty use: 11 kW, 46.2 A. Light-overload use: 15 kW, 59 A. All at 200–240 V three-phase input.

What enclosure protection does it have?

IP55 and NEMA Type 12 — dust-tight and protected against hose-down water, suitable for wall-mounting in wet or dusty environments.

What communication protocol does it use?

CAN-based communication. No onboard Ethernet; fieldbus option modules are required for protocols like Modbus TCP or PROFINET.

What compliance documentation is available?

RoHS compliant per 2011/65/EU (date 20240508). REACH declaration (date 20250905) confirms substances above 0.1% mass. SCIP number 2f1b7d72-3cb1-49a1-82e4-a721459937d4 Finland is on file.

MPN
3AXD50000418176