The 3AXD50000418213: The normal-use current (171 A) is the figure to match against your motor FLA for continuous duty; the heavy-duty curve (143 A) governs for pumps or conveyors that cycle hard. Input range is 200…240 V three-phase, so it's a low-voltage drive — not for 400 V supplies. Efficiency sits at IE2, with a power factor of 0.98 and standby loss of 22 W. The 47.5…63 Hz input frequency covers 50 and 60 Hz grids.
I/O and communications
The drive includes 2 analog inputs, 2 analog outputs, 6 digital inputs, and 3 digital outputs — enough for basic pump control, level sensing, and feedback without an expansion module. Communication is CAN-based; there are no onboard industrial Ethernet interfaces, so if your plant uses PROFINET or EtherNet/IP, plan for an optional fieldbus adapter. The control unit is included.
Sourcing
This is an active, current-production drive. No last-time-buy or phase-out notice applies.