Light-overload rating lands at 211 A output current, good for 75 Hp; heavy-duty use drops to 169 A and 60 Hp. Frame size R7, NEMA Type 1 enclosure with IP21 protection.
Heavy-duty (169 A) applies for constant-torque loads like extruders or positive-displacement pumps where the drive must hold rated current through the full speed range. Both ratings are UL-listed, so the drive carries a UL mark for North American panel builds.
Enclosure & Mounting
NEMA Type 1 with IP21 means the drive is suitable for indoor use where falling dirt and dripping water are not an issue. Frame R7 is a larger footprint — plan for floor-mount or a substantial backplate; this is not a DIN-rail unit. The integrated disconnect means one less external component in the panel, but verify the disconnect rating against your branch-circuit SCCR requirements.