Skip to main content
ABB 3AXD50000462483 — AC Drive (VFD) 240V

ABB 3AXD50000462483 ACS580 Drive, 211 A, 75 Hp, 240 V

MPN3AXD50000462483
Active

ABB ACS580 LV AC Packaged Drive, 3AXD50000462483, 3-phase, 208-240 V, 211 A light-overload, 75 Hp, NEMA Type 1, IP21, Frame R7.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Electrical Input

3AXD50000462483 — Electrical Input
ParameterValue
Input voltage range208 ... 240 V
Number of phases3-phase
Frequency50/60 Hz

Electrical Output

3AXD50000462483 — Electrical Output
ParameterValue
Output power, heavy duty (UL, Hp)60 Hp
Output current, heavy duty (UL)169 A
Output power, light-overload duty (UL, Hp)75 Hp
Output current, light-overload duty (UL)211 A

Mechanical

3AXD50000462483 — Mechanical
ParameterValue
Degree of protection (IP)IP21
Enclosure type (NEMA)Type1
Frame sizeR7

Product details

Light-overload rating lands at 211 A output current, good for 75 Hp; heavy-duty use drops to 169 A and 60 Hp. Frame size R7, NEMA Type 1 enclosure with IP21 protection.

Heavy-duty (169 A) applies for constant-torque loads like extruders or positive-displacement pumps where the drive must hold rated current through the full speed range. Both ratings are UL-listed, so the drive carries a UL mark for North American panel builds.

Enclosure & Mounting

NEMA Type 1 with IP21 means the drive is suitable for indoor use where falling dirt and dripping water are not an issue. Frame R7 is a larger footprint — plan for floor-mount or a substantial backplate; this is not a DIN-rail unit. The integrated disconnect means one less external component in the panel, but verify the disconnect rating against your branch-circuit SCCR requirements.

Frequently asked questions

What is the frame size of this drive?

Frame size R7.

MPN