The ABB 3AXD50000463305 is an ACS580 LV AC packaged drive with an integrated disconnect means, rated for 3-phase input at 525 to 575 V, 50/60 Hz. Frame size R2. The UL heavy-duty rating is 3 Hp at 3.9 A; the light-overload rating is 5 Hp at 6.1 A. That means for a constant-torque load like a conveyor or positive-displacement pump, size to the heavy-duty current; for a variable-torque fan or centrifugal pump, the light-overload figure governs the continuous rating.
NEMA Type 1 enclosure with IP21 ingress protection. Suitable for indoor, non-condensing environments. The R2 frame accepts standard panel-mounting on a backplate; the disconnect handle protrudes through the enclosure door. Verify gland-plate clearance for the incoming 525–575 V supply — the disconnect terminals require 6 AWG minimum per UL 508A.