Skip to main content
ABB 3AXD50000463305 — AC Drive (VFD) 600V

ABB 3AXD50000463305 ACS580 Drive, 5 Hp, 6.1 A, 600 V

MPN3AXD50000463305
Active

ABB ACS580 LV AC Packaged Drive with disconnect means, 3AXD50000463305, 5 Hp light-overload UL, 6.1 A, 600 V, frame R2, NEMA 1, IP21.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3AXD50000463305 — Identification
ParameterValue
Frame sizeR2
3AXD50000463305 — Electrical (input)
ParameterValue
Input voltage range525 ... 575 V
Number of phases3-phase
Frequency range50/60 Hz
3AXD50000463305 — Output / Performance
ParameterValue
Output power (UL), light overload5 Hp
Output power (UL), heavy duty3 Hp
Output current (UL), light overload6.1 A
Output current (UL), heavy duty3.9 A
3AXD50000463305 — Mechanical
ParameterValue
NEMA enclosure typeType1
3AXD50000463305 — Environmental
ParameterValue
Degree of protection (IEC, IP)IP21

Product details

The ABB 3AXD50000463305 is an ACS580 LV AC packaged drive with an integrated disconnect means, rated for 3-phase input at 525 to 575 V, 50/60 Hz. Frame size R2. The UL heavy-duty rating is 3 Hp at 3.9 A; the light-overload rating is 5 Hp at 6.1 A. That means for a constant-torque load like a conveyor or positive-displacement pump, size to the heavy-duty current; for a variable-torque fan or centrifugal pump, the light-overload figure governs the continuous rating.

NEMA Type 1 enclosure with IP21 ingress protection. Suitable for indoor, non-condensing environments. The R2 frame accepts standard panel-mounting on a backplate; the disconnect handle protrudes through the enclosure door. Verify gland-plate clearance for the incoming 525–575 V supply — the disconnect terminals require 6 AWG minimum per UL 508A.

Frequently asked questions

What are the UL ratings for this drive?

Heavy-duty UL: 3 Hp, 3.9 A. Light-overload UL: 5 Hp, 6.1 A. Input voltage is 525–575 V three-phase at 50/60 Hz.

What frame size is 3AXD50000463305?

Frame size R2.

What enclosure type and IP rating does this drive have?

NEMA Type 1 enclosure with IP21 protection.

MPN