Skip to main content
ABB 3AXD50000463411 — AC Drive (VFD) 600V

ABB 3AXD50000463411 ACS580-0P-099A-6, 100 HP, 99 A, 600 V

MPN3AXD50000463411
Active

ABB ACS580-0P-099A-6, LV AC Packaged drive with disconnect, 100 Hp light-overload, 99 A, 600 V, Frame Size R7.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3AXD50000463411 — Identification
ParameterValue
Frame sizeR7
3AXD50000463411 — Electrical (input)
ParameterValue
Input voltage range525 ... 575 V
Number of phases3-phase
Frequency range50/60 Hz
3AXD50000463411 — Output / Performance
ParameterValue
Output power (UL), light overload100 Hp
Output power (UL), heavy duty75 Hp
Output current (UL), light overload99 A
Output current (UL), heavy duty77 A
3AXD50000463411 — Mechanical
ParameterValue
NEMA enclosure typeType1
3AXD50000463411 — Environmental
ParameterValue
Degree of protection (IEC, IP)IP21

Product details

The ABB 3AXD50000463411 is an ACS580-0P-099A-6 LV AC packaged drive with an integrated disconnect means — a single enclosure that handles both power conversion and disconnection, saving panel space and wiring. It's rated for 3-phase input at 525 to 575 V, 50/60 Hz, and delivers 99 A in light-overload use (100 Hp) or 77 A in heavy-duty use (75 Hp) per UL. The R7 frame size and IP21 / NEMA Type 1 enclosure mean it's built for indoor installation with basic splash protection, not washdown environments.

The heavy-duty current of 77 A sets the real-world limit for continuous motor load on a constant-torque application like a conveyor or extruder. The light-overload rating (99 A) is for variable-torque loads — fans, pumps — where the drive can deliver higher current because the thermal duty cycle is less demanding. The 525–575 V input range covers 480 V and 600 V class systems; at 575 V you get the full 100 Hp output without derating. The R7 frame is a standardized ABB footprint; if you're swapping into an existing R7 panel cutout, it fits without mechanical modification.

Frequently asked questions

What is the frame size of this drive?

The frame size is R7, which is a standard ABB enclosure size for this power class.

What input voltage and frequency does it accept?

It accepts 3-phase 525 to 575 V at 50/60 Hz.

What are the heavy-duty and light-overload current ratings?

Heavy-duty (constant torque): 77 A, 75 Hp. Light-overload (variable torque): 99 A, 100 Hp.

MPN
3AXD50000463411