Electrical Input

3AXD50000465781 — Electrical Input
ParameterValue
Input voltage range208 ... 240 V
Number of phases3-phase
Frequency50/60 Hz

Electrical Output

3AXD50000465781 — Electrical Output
ParameterValue
Output power, light-overload duty (UL, Hp)10 Hp
Output current, light-overload duty (UL)30.8 A

Mechanical

3AXD50000465781 — Mechanical
ParameterValue
Degree of protection (IP)IP21
Enclosure type (NEMA)Type1
Frame sizeR2

Product details

The ABB 3AXD50000465781 is an LV AC packaged drive with disconnect and fuses, built for 3-phase 208-240 V input at 50/60 Hz. It carries a UL light-overload rating of 10 Hp and 30.8 A output, housed in a Frame R2 enclosure rated NEMA Type 1 and IP21.

This drive is a self-contained unit with integrated disconnect and fuses, saving panel space and wiring compared to a bare VFD plus separate branch protection. The 30.8 A light-overload rating suits constant-torque loads like conveyors or pumps up to 10 Hp; for variable-torque (fan/pump) duty, the same frame can typically carry a higher horsepower rating, but the UL listing here is the binding spec for North American installations.

The product lifecycle is marked active (current), meaning ABB continues to manufacture and support this order code. For BOM freeze or multi-year projects, this is a stable line-item with standard supply continuity.

Frame R2 is a compact footprint for a packaged drive with disconnect. NEMA Type 1 (IP21) allows indoor installation in dry, non-hazardous locations — no drip shield needed, but keep it away from washdown zones. The 50/60 Hz rating covers global line frequencies, though the input voltage range (208-240 V) limits it to North American 208/230/240 V three-phase networks.

Sourcing this drive to order against an RFQ is straightforward given its active status. The integrated disconnect and fuses simplify compliance with NEC branch-circuit requirements, and the UL listing eases panel acceptance for UL 508A shops.

Frequently asked questions

What is the frame size of this drive?

The frame size is R2, which is the mechanical package size for this ACQ580-PD series.

What input voltage and frequency does this drive accept?

It accepts 3-phase 208-240 V input at 50/60 Hz.

What enclosure type and protection rating does it have?

NEMA Type 1 enclosure with IP21 degree of protection, suitable for indoor dry locations.