The ABB 3AXD50000705665 is a low-voltage AC packaged drive that comes with a disconnect switch and fuses already integrated. UL-listed for light-overload use at 15 Hp, 17 A, on a 575 V supply, it's built for 3-phase 50/60 Hz systems.
The 15 Hp light-overload rating is the number that matters for sizing the motor. Light-overload means 110 % current capability for 1 minute every 10 minutes — enough for a pump or fan that doesn't need a heavy starting surge. The 17 A output current at 575 V matches a standard NEMA 15 Hp motor frame. The 525–600 V input range covers 480 V systems with a step-up transformer, but more commonly lands on 575 V or 600 V plant distribution. The NEMA 3R enclosure gives you rain-tight and sleet-resistant protection; it's not submersible, but it'll handle a hose-down from the side.