Duty ratings and real-world fit
The 3AXD50000716388: The 9.8 A light-overload current (IlD) defines the continuous rating for typical fan/pump profiles; the 7.5 A heavy-duty current (IhD) applies for constant-torque loads like conveyors or extruders. The 0.98 power factor reflects the input stage, not the motor — expect near-unity displacement at rated load. Sound level is 51.8 dB(A), typical for a frame R1 module at full fan speed.
Onboard I/O includes 2 analog inputs, 1 analog output, 4 digital inputs, and 2 digital outputs — sufficient for basic speed reference and run/stop control. Communication is fixed to MODBUS; no Industrial Ethernet interface is present (0 hardware interfaces for Ethernet). The module includes the control unit, so no separate controller purchase is needed.
Frame size R1, module mounting, IP20 enclosure (Open Type per NEMA). Operating humidity 5–95% RH non-condensing. The WEEE category is 5 (Small Equipment, <50 cm external dimension).