It delivers 0.55 kW normal-use output at 3.7 A from a 200-240 V single-phase supply, with a heavy-duty rating of 0.37 kW at 2.4 A.
Duty Ratings and Load Profiles
Three duty ratings let you match the drive to the application: normal use (Pn) at 0.55 kW / 3.7 A, light-overload (PlD) at 0.55 kW / 3.5 A, and heavy-duty (PhD) at 0.37 kW / 2.4 A. The UL listing mirrors these with 0.75 Hp normal and light-overload, and 0.5 Hp heavy-duty. For a constant-torque conveyor or pump, size on the heavy-duty current; for variable-torque fans, the normal-use figure gives more headroom.
Input and Environment
Runs on a single-phase 200-240 VAC input at 47-63 Hz, drawing 42 W typical power consumption. The apparent power output is rated at 1.5 kV·A. Enclosure is IP20 (open type per NEMA), so it's for panel-mount indoor use where it won't see washdown or dust. Altitude limit is 2000 m without derating.
Onboard I/O includes 2 analog inputs, 1 analog output, and 4 digital inputs with 2 digital outputs. Communication is MODBUS over the built-in interface — no Industrial Ethernet on this variant, so plan for a serial or gateway connection if the network is PROFINET or EtherNet/IP.