Skip to main content
ABB 3AXD50000760947 — AC Drive (VFD) 240V

ABB 3AXD50000760947 ACQ580-01-059A-2 Drive, 20 Hp, 59 A, 230

MPN3AXD50000760947
Active

ABB ACQ580-01-059A-2, LV AC wall-mounted drive, 20 Hp light-overload, 59 A, 208-240 V, 3-phase, IP21, NEMA 1, Frame R3.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Electrical Input

3AXD50000760947 — Electrical Input
ParameterValue
Input voltage range208 ... 240 V
Number of phases3-phase
Frequency50/60 Hz

Electrical Output

3AXD50000760947 — Electrical Output
ParameterValue
Output power, heavy duty (UL, Hp)15 Hp
Output current, heavy duty (UL)15 A
Output power, light-overload duty (UL, Hp)20 Hp
Output current, light-overload duty (UL)59 A

Mechanical

3AXD50000760947 — Mechanical
ParameterValue
Degree of protection (IP)IP21
Enclosure type (NEMA)Type1
Frame sizeR3

Product details

The ABB 3AXD50000760947 is the ACQ580-01-059A-2, a wall-mounted LV AC drive built for water and wastewater applications. It runs on a 208-240 V three-phase supply at 50/60 Hz and delivers 20 Hp with 59 A in light-overload use, or 15 Hp at 15 A for heavy-duty cycles. The R3 frame keeps the footprint manageable for panel layouts where NEMA 1 and IP21 are specified.

Duty ratings and real-world fit

The light-overload rating of 59 A is the number to size by for pump and fan profiles — it gives you headroom for variable-torque starts without oversizing the drive. Both are UL-listed, so the drive lands cleanly in a UL 508A panel without a derating fight.

NEMA 1 enclosure with IP21 protection means it's suitable for indoor, non-condensing environments — typical for a pump room or treatment gallery. Wall-mount the R3 frame with clearance above and below for airflow; the IP21 rating doesn't tolerate washdown, so keep it out of the spray zone.

Frequently asked questions

What are the key ratings for this drive?

Light-overload: 20 Hp, 59 A. Heavy-duty: 15 Hp, 15 A. Input: 208-240 V, 3-phase, 50/60 Hz. Frame R3, NEMA 1, IP21.

What enclosure and protection rating does it have?

NEMA Type 1 enclosure with IP21 degree of protection. Suitable for indoor, dry locations.

MPN
3AXD50000760947