Skip to main content
ABB 3AXD50000761128 — AC Drive (VFD) 600V

ABB 3AXD50000761128 ACQ580-01 VFD, 2 Hp, 2.7 A, 575 V

MPN3AXD50000761128
Active

ABB ACQ580-01 wall-mounted LV AC drive, 3-phase, 525-600 V input, UL light-overload 2 Hp / 2.7 A, IP55, NEMA 12.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3AXD50000761128 — Identification
ParameterValue
Frame sizeUndefined
3AXD50000761128 — Electrical (input)
ParameterValue
Input voltage range525 ... 600 V
Number of phases3-phase
Frequency range50/60 Hz
3AXD50000761128 — Output / Performance
ParameterValue
Output power (UL), light overload2 Hp
Output power (UL), heavy duty1.5 Hp
Output current (UL), light overload2.7 A
Output current (UL), heavy duty1.5 A
3AXD50000761128 — Mechanical
ParameterValue
NEMA enclosure typeType12
3AXD50000761128 — Environmental
ParameterValue
Degree of protection (IEC, IP)IP55

Product details

The ABB 3AXD50000761128 is an ACQ580-01 wall-mounted LV AC drive, built for water and wastewater applications. It accepts 3-phase input at 525 to 600 V, 50/60 Hz, and delivers UL light-overload output of 2 Hp at 2.7 A, or 1.5 Hp heavy-duty at 1.5 A. The enclosure is IP55 with NEMA Type12 rating, suited for washdown or dusty environments without an additional cabinet.

The UL heavy-duty rating (1.5 Hp, 1.5 A) governs continuous motor operation at rated current — that is the number to use for a constant-torque pump or fan application where the load stays near nameplate. The light-overload rating (2 Hp, 2.7 A) allows a 33 % current margin for 60-second overloads, typical for variable-torque loads like centrifugal pumps. The 525-600 V input range covers 480 V and 575 V nominal systems with margin; confirm your supply voltage falls within this band.

Wall-mount design with IP55 / NEMA 12 protection. This means the drive can be installed directly in a non-conditioned area with dust or hose-down exposure, as long as it is not submerged. No separate enclosure is required for most indoor water-treatment environments. Verify the ambient temperature range in the full datasheet before final placement.

Frequently asked questions

What are the key electrical ratings for this drive?

Input is 3-phase, 525-600 V, 50/60 Hz. UL heavy-duty output is 1.5 Hp at 1.5 A; UL light-overload output is 2 Hp at 2.7 A.

What enclosure protection does this drive have?

IP55 and NEMA Type12, suitable for indoor locations with dust or water spray.

MPN
3AXD50000761128