The 3AXD50000956685: Built-in BACnet communication makes it a direct fit for building management system integration without an external gateway. The R1 frame size keeps panel footprint compact, and the IP20 enclosure suits clean indoor cabinet mounting.
Normal-use output current of 6.9 A (In) matches a standard 1.1 kW induction motor. Heavy-duty curve drops to 4.6 A (IhD) at 0.75 kW for continuous cyclic loads. Light-overload use holds at 1.1 kW with 6.6 A output for variable-torque fans and pumps. UL ratings: 1.5 Hp normal duty at 6.6 A, 1.0 Hp heavy-duty at 4.6 A. The drive accepts 200-240 V at 47.5-63 Hz. Standby loss is 7 W. Maximum ambient temperature is 60 °C. Altitude rating is 2000 m.
I/O and control integration
The control unit includes 2 analog inputs, 1 analog output, and 4 digital inputs plus 2 digital outputs — enough for basic speed reference, run/stop, and fault feedback without an expansion module. The single BACnet MS/TP port handles the building automation link; there is no second Ethernet port, so daisy-chaining requires an external switch.
UL listing covers Open Type enclosure for panel mounting. WEEE category 5 (small equipment) applies for end-of-life take-back in EU markets.