ABB 3AXD50000956722 — AC Drive (VFD) 240V

ABB 3AXD50000956722 ACH180 Micro Drive, 4.0 kW, 17.5 A, 230

MPN3AXD50000956722
Active

ABB ACH180 series micro drive, 3AXD50000956722, 4.0 kW / 17.5 A normal use, 200-240 V 3-phase input, IP20, BACnet, frame R2.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Electrical Output

3AXD50000956722 — Electrical Output
ParameterValue
Output power, normal duty (Pn)4.0 kW
Output current, normal duty (In)17.5 A
Output power, heavy duty (PhD)3.0 kW
Output current, heavy duty (IhD)14.6 A
Output power, light-overload duty (PlD)4.0 kW
Output current, light-overload duty (IlD)16.7 A
Output power, heavy duty (UL, Hp)4.0 Hp
Output current, heavy duty (UL)12.2 A
Apparent power output7.0 kV·A
Output power, light-overload duty (UL, Hp)5.0 Hp
Efficiency class (IE)IE2
Output current, light-overload duty (UL)16.7 A
Standby loss9 W

Electrical Input

3AXD50000956722 — Electrical Input
ParameterValue
Input voltage range200 ... 240 V
Number of phases3-phase
Frequency47.5 ... 63 Hz
Power factor0.98

Control & I/O

3AXD50000956722 — Control & I/O
ParameterValue
Digital inputs / outputs4 / 2
Communication protocolBACNET
Analog inputs2
Analog outputs1
Hardware interfacesIndustrial Ethernet 0

Environmental

3AXD50000956722 — Environmental
ParameterValue
Temperature rating, max.Maximum 60 °C
Altitude2000 m
Noise level62.00 dB(A)

Mechanical

3AXD50000956722 — Mechanical
ParameterValue
Degree of protection (IP)IP20
Enclosure type (NEMA)Open Type
Frame sizeR2
Mounting typeModule

Approvals

3AXD50000956722 — Approvals
ParameterValue
RoHS complianceFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
REACH complianceTrue - contains substances > 0.1 mass percentage

Product details

The 3AXD50000956722 is an ABB ACH180 micro drive in frame R2, rated for 4.0 kW normal-use output (17.5 A) on 200-240 V three-phase input. Light-overload use (variable-torque HVAC fans and centrifugal pumps) is 4.0 kW (16.7 A). BACnet communication is onboard, so no separate gateway is needed for BAS integration.

Integration points

Two analog inputs, one analog output. Four digital inputs, two digital outputs — enough for basic start/stop, speed reference, and fault reset. No industrial Ethernet interface on this variant; BACnet is the only fieldbus. Frequency range 47.5-63 Hz covers 50/60 Hz mains. Maximum ambient temperature 60 °C, but sound level is 62 dB(A) — audible in a quiet mechanical room. Frame R2 is a module mount; plan for DIN-rail or backplate with clearance for airflow.

Frequently asked questions

What is the altitude rating?

2000 m without derating. Above that, consult the drive manual for power reduction.

What is the SCIP number?

40922a0b-ac0b-46c4-8517-b1d36d17a369 Finland.

MPN