ABB 3AXD50001002626 — AC Drive (VFD) 240V

ABB 3AXD50001002626 ACH580-01 HVAC Drive, 1.5 kW, 7.6 A, 230

MPN3AXD50001002626
Active

ABB ACH580-01 HVAC drive, 3AXD50001002626, 1.5 kW / 7.6 A normal use, 200–240 V, 3-phase, IP66, NEMA 4X, BACnet, frame R1, wall-mounted, includes control unit.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3AXD50001002626 — Electrical Output
ParameterValue
Output power, normal duty (Pn)1.5 kW
Output current, normal duty (In)7.6 A
Output power, heavy duty (PhD)1.1 kW
Output current, heavy duty (IhD)6.6 A
Output power, light-overload duty (PlD)1.5 kW
Output current, light-overload duty (IlD)7.5 A
Apparent power output3.0 kV·A
Output power, light-overload duty (UL, Hp)2 Hp
Efficiency class (IE)IE2
Output current, light-overload duty (UL)7.5 A
Standby loss13 W
3AXD50001002626 — Electrical Input
ParameterValue
Input voltage range200 ... 240 V
Number of phases3-phase
Frequency47.5 ... 63 Hz
Power factor0.98
3AXD50001002626 — Control & I/O
ParameterValue
Digital inputs / outputs6 / 3
Communication protocolBACNET
Analog inputs2
Analog outputs2
Hardware interfacesIndustrial Ethernet 0
3AXD50001002626 — Environmental
ParameterValue
Temperature rating, max.Maximum 40 °C
3AXD50001002626 — Mechanical
ParameterValue
Degree of protection (IP)IP66
Enclosure type (NEMA)Type4X
Frame sizeR1
Mounting typeWall-mounted

Product details

Drive ratings and deployment context

The ABB 3AXD50001002626 is an ACH580-01 wall-mounted HVAC drive rated for 1.5 kW normal-use output (Pn) at 7.6 A (In) on a 200–240 V three-phase supply, with a heavy-duty rating of 1.1 kW (PhD) at 6.6 A (IhD). The IP66 and NEMA 4X enclosure means the drive is sealed against hose-directed water and corrosion — suitable for outdoor rooftop units, washdown areas in food processing, or coastal installations where salt spray is a concern. Built-in BACnet MS/TP communication allows direct integration into building management systems without an external gateway, matching the typical fieldbus requirement for HVAC retrofit or new construction.

Efficiency and standby loss

Rated IE2 efficiency level and a standby loss of 13 W — the standby figure governs the continuous power draw when the motor is stopped but the drive remains powered, relevant for energy code compliance in continuously occupied spaces.

I/O and control interface

The drive includes 2 analog inputs and 2 analog outputs, plus 6 digital inputs and 3 digital outputs — sufficient for a typical HVAC sequence (supply fan, return fan, economizer, duct static pressure sensor, space temperature sensor) without an expansion module.

Frequently asked questions

What compliance documentation does ABB provide for 3AXD50001002626?

The drive carries UL listing per the UL ratings (2 Hp, 7.5 A at 240 V) and IEC ratings (1.5 kW, 7.6 A at 230 V). RoHS and REACH declarations are standard for ABB drives of this series, though specific certificates are not in this evidence set.

MPN
3AXD50001002626