The 3AXD50001002640 is the control-unit variant of a wall-mounted HVAC drive, frame size R2. It ships with the control unit included. Rated for 5.5 kW normal duty (24.5 A) and 4 kW heavy-duty (16.7 A) on a 200-240 V three-phase supply, 47.5-63 Hz. The IP66 / NEMA 4X enclosure means it stands up to washdown environments without an extra cabinet.
Normal-use output current of 24.5 A (24 A UL) sets the motor full-load amp ceiling for continuous duty. Heavy-duty cycle drops to 16.7 A — that's the number to check if the load profile includes frequent starts or overloads. Standby loss is 14 W, so the heat load in a sealed panel is modest. Power factor is 0.98, which keeps the input current low relative to real power.
Integration checklist
Wall-mounted, frame R2. Two analog inputs and two analog outputs are on board. Six digital inputs and three digital outputs handle start/stop, fault reset, and status feedback. BACnet communication is built in — no option card required for BAS integration. The lithium coin cell (CR2032, 220 mAh) keeps the real-time clock alive during power loss.