The ABB 3AXD50001004675 is an ACH580-01 wall-mounted HVAC drive rated 3 kW normal-use output at 12 A, with heavy-duty capability at 2.2 kW / 7.5 A. It runs on 200-240 V three-phase input across 47.5-63 Hz. The package includes the control unit, so no separate controller card is needed — one order code lands a complete drive.
The normal-use (light-overload) current is 11.8 A, while the heavy-duty line drops to 7.5 A. For UL-listed installations the light-overload output is 3 Hp at 10.6 A. The IE2 efficiency level and 0.98 power factor are typical for this class — the standby loss of 13 W matters if the drive idles for long periods in a multi-unit bank.
IP66 and NEMA 4X rating means it handles washdown and outdoor installation without an extra cabinet. The maximum ambient is 40 °C — derate above that. Wall-mounted in frame size R1, so it fits a compact footprint. The lithium coin cell (CR2032, 220 mAh) keeps the real-time clock and parameter backup alive during power loss.
Two analog inputs and two analog outputs cover the typical pressure/temperature/flow feedback loop. Six digital inputs and three digital outputs handle start/stop, fault reset, and run indication. BACnet is the onboard protocol — no option card needed for BMS integration. There is no industrial Ethernet interface, so if you need Modbus TCP or PROFINET, that requires a separate fieldbus adapter.