Drive ratings and duty selection
The ABB 3AXD50001071721 is an ACS280-04S-12A2-1 drive in frame size R2, fed from a 208-240 V single-phase line. Normal-use output is rated 3 kW at 12.2 A; for heavy-duty applications the rating drops to 2.2 kW at 9.8 A. A light-overload duty cycle is also specified at 3 kW, 11.6 A — the same power as normal use but with a slightly lower current limit, which suggests a different thermal profile or load type. The 47.5-63 Hz input range covers 50/60 Hz grids without derating.
The drive is a module-type unit with IP00 protection and an open-type NEMA enclosure. That means it requires a clean, dry cabinet — no washdown or dust-tight environment. Frame size R2 is the physical footprint; verify panel depth and DIN-rail or screw-mount compatibility against the ACS280 mechanical drawing before laying out the gland plate.
Efficiency class is IE2, which meets the minimum for most industrial applications in regions where IE2 is still permitted for variable-torque loads. The SCIP number f55327d4-7fdf-4531-ac98-faed9ea4b11e Finland is on record — relevant for EU REACH/SCIP substance reporting.