On a 208-240 V supply, that current supports a 25 Hp induction motor in typical HVAC fan or pump duty. Frame R6 determines the mounting footprint and conduit knockouts. NEMA Type 1 and IP21 mean the drive is suitable for indoor, non-condensing environments — no washdown or dust-tight rating. If the installation is in a conditioned electrical room, this enclosure is fine; if it's near a cooling tower or in a partially sheltered mezzanine, plan for a higher IP enclosure or a separate cabinet.
ABB 3AXD50001076412 ACH580-31 Drive, 25 Hp, 74.8 A, 230 V
MPN3AXD50001076412
Active
ABB ACH580-31 ultra-low harmonic drive, 3-phase 208-240 V, 25 Hp light-overload, 74.8 A, frame R6, NEMA 1, IP21.
StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →Specifications
Electrical Input
| Parameter | Value |
|---|---|
| Input voltage range | 208 ... 240 V |
| Number of phases | 3-phase |
| Frequency | 50/60 Hz |
Electrical Output
| Parameter | Value |
|---|---|
| Output power, light-overload duty (UL, Hp) | 25 Hp |
| Output current, light-overload duty (UL) | 74.8 A |
Mechanical
| Parameter | Value |
|---|---|
| Degree of protection (IP) | IP21 |
| Enclosure type (NEMA) | Type1 |
| Frame size | R6 |
Product details
Frequently asked questions
What is the frame size of 3AXD50001076412?
Frame size R6.
What is the frequency rating of 3AXD50001076412?
50/60 Hz.
What is the light-overload output current and power?
Light-overload use (UL) is rated at 25 Hp and 74.8 A.
What input voltage and phases does this drive require?
Three-phase, 208-240 V.
MPN