Skip to main content
ABB 3AXD50001108908 — AC Drive (VFD) 240V

ABB 3AXD50001108908 ACS580-01 Drive, 0.75 kW, IP66

MPN3AXD50001108908
Active

ABB ACS580-01 wall-mounted LV AC drive, 3-phase 200-240 V, 0.75 kW (1 Hp), 4.7 A, IP66/NEMA 4X, includes control unit.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3AXD50001108908 — Electrical Output
ParameterValue
Output power, normal duty (Pn)0.75 kW
Output current, normal duty (In)4.7 A
Output power, heavy duty (PhD)0.55 kW
Output current, heavy duty (IhD)3.5 A
Output power, light-overload duty (PlD)0.75 kW
Output current, light-overload duty (IlD)4.6 A
Apparent power output1.9 kV·A
Output power, light-overload duty (UL, Hp)1 Hp
Efficiency class (IE)IE2
Output current, light-overload duty (UL)4.6 A
Standby loss13 W
3AXD50001108908 — Electrical Input
ParameterValue
Input voltage range200 ... 240 V
Number of phases3-phase
Frequency47.5 ... 63 Hz
Power factor0.98
3AXD50001108908 — Control & I/O
ParameterValue
Digital inputs / outputs6 / 3
Communication protocolCAN
Analog inputs2
Analog outputs2
Hardware interfacesIndustrial Ethernet 0
3AXD50001108908 — Environmental
ParameterValue
Temperature rating, max.Maximum 40 °C
3AXD50001108908 — Mechanical
ParameterValue
Degree of protection (IP)IP66
Enclosure type (NEMA)Type4X
Mounting typeWall-mounted

Product details

The 3AXD50001108908: The drive carries three duty ratings. Normal use (Pn) is 0.75 kW at 4.7 A — that's the continuous rating for a standard variable-torque load like a fan or pump. Heavy-duty use (PhD) drops to 0.55 kW at 3.5 A, which covers constant-torque applications such as conveyors or extruders where the motor pulls full current across the speed range. Light-overload use (PlD) matches the normal-use power at 0.75 kW but at a slightly lower 4.6 A, and the UL listing assigns 1 Hp at 4.6 A for North American motor frames.

The drive includes 2 analog inputs and 2 analog outputs for speed reference or process feedback, plus 6 digital inputs and 3 digital outputs. Communication is via CAN — no onboard Industrial Ethernet, so if your plant runs PROFINET or EtherNet/IP you'll need a fieldbus adapter module. The control unit is included in the package, so you're not buying a bare power stage; it arrives ready to commission.

Efficiency and standby

Rated IE2 efficiency with a power factor of 0.98. Standby loss is 13 W — modest enough that leaving the drive powered when the motor is stopped won't run up the electric bill, but worth factoring into a panel's thermal budget if multiple drives sit in a sealed enclosure.

Frequently asked questions

What is the included control unit?

The drive ships with the control unit included — it is not a bare power stage. The order code covers the complete wall-mounted drive ready for commissioning.

What are the key ratings for this drive?

Normal-duty output is 0.75 kW at 4.7 A on 200-240 V three-phase. Heavy-duty output is 0.55 kW at 3.5 A. The enclosure is IP66 / NEMA 4X, rated for washdown environments.

What communication protocol does it use?

The drive uses CAN for fieldbus communication. There is no onboard Industrial Ethernet port.

MPN
3AXD50001108908