The 3AXD50001109264 is an ABB ACS580-01 wall-mounted drive rated for a 7.5 kW normal-duty motor on 200–240 V three-phase input, delivering 31.2 A continuous output. Heavy-duty use drops to 5.5 kW / 24.2 A for constant-torque loads like conveyors or extruders. The IP66 / NEMA 4X enclosure lets it mount directly on the machine frame or washdown area without a separate cabinet. Built-in CAN communication handles peer-to-peer or drive-to-PLC links; no industrial Ethernet port on this variant, so plan for a fieldbus adapter if your backbone is PROFINET or EtherNet/IP. The 6 digital inputs and 3 digital outputs cover basic start/stop, fault reset, and speed reference switching without an extra I/O block. Standby loss of 14 W keeps the panel cool when the motor is idle. Power factor of 0.98 at rated load means minimal reactive current draw — no need for external PFC caps on most lines.
3AXD50001109264 ACS580-01-032A-2+B063+F253 VFD, 7.5 kW, 31.2
ABB ACS580-01 wall-mounted drive, 3AXD50001109264, 7.5 kW / 31.2 A normal duty, 200–240 V 3-phase, IP66/NEMA 4X, IE2, includes control unit.
Specifications
| Parameter | Value |
|---|---|
| Output power, normal duty (Pn) | 7.5 kW |
| Output current, normal duty (In) | 31.2 A |
| Output power, heavy duty (PhD) | 5.5 kW |
| Output current, heavy duty (IhD) | 24.2 A |
| Output power, light-overload duty (PlD) | 7.5 kW |
| Output current, light-overload duty (IlD) | 30.8 A |
| Apparent power output | 11.8 kV·A |
| Output power, light-overload duty (UL, Hp) | 10 Hp |
| Efficiency class (IE) | IE2 |
| Output current, light-overload duty (UL) | 31 A |
| Standby loss | 14 W |
| Parameter | Value |
|---|---|
| Input voltage range | 200 ... 240 V |
| Number of phases | 3-phase |
| Frequency | 47.5 ... 63 Hz |
| Power factor | 0.98 |
| Parameter | Value |
|---|---|
| Digital inputs / outputs | 6 / 3 |
| Communication protocol | CAN |
| Analog inputs | 2 |
| Analog outputs | 2 |
| Hardware interfaces | Industrial Ethernet 0 |
| Parameter | Value |
|---|---|
| Temperature rating, max. | Maximum 40 °C |
| Parameter | Value |
|---|---|
| Degree of protection (IP) | IP66 |
| Enclosure type (NEMA) | Type4X |
| Mounting type | Wall-mounted |
Product details
Frequently asked questions
What are the key ratings for this drive?
Normal-duty output is 7.5 kW / 31.2 A; heavy-duty output is 5.5 kW / 24.2 A. Input voltage is 200–240 V three-phase, 47.5–63 Hz. The enclosure is IP66 / NEMA 4X, rated for ambient temperatures up to 40 °C.
What is included with this order code?
The listing includes a control unit. The drive also contains a CR2032 lithium coin cell (220 mAh, 3 V) for parameter backup.
Does this drive have industrial Ethernet onboard?
No. The hardware interfaces list shows 0 industrial Ethernet ports. Communication is via CAN; add an optional fieldbus adapter for Ethernet-based networks.