Skip to main content
ABB 3AXD50001109462 — AC Drive (VFD) 240V

ABB 3AXD50001109462 ACQ580-01 Drive, 5.5 kW, IP66

MPN3AXD50001109462
Active

ABB ACQ580-01 wall-mounted drive, 5.5 kW, 24.5 A, 200-240 V, IP66/NEMA 4X, includes control unit.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3AXD50001109462 — Electrical Output
ParameterValue
Output power, normal duty (Pn)5.5 kW
Output current, normal duty (In)24.5 A
Output power, heavy duty (PhD)4 kW
Output current, heavy duty (IhD)16.7 A
Output power, light-overload duty (PlD)5.5 kW
Output current, light-overload duty (IlD)24.2 A
Apparent power output9.8 kV·A
Output power, light-overload duty (UL, Hp)7.5 Hp
Efficiency class (IE)IE2
Output current, light-overload duty (UL)24 A
Standby loss14 W
3AXD50001109462 — Electrical Input
ParameterValue
Input voltage range200 ... 240 V
Number of phases3-phase
Frequency47.5 ... 63 Hz
Power factor0.98
3AXD50001109462 — Control & I/O
ParameterValue
Digital inputs / outputs6 / 3
Communication protocolCAN
Analog inputs2
Analog outputs2
Hardware interfacesIndustrial Ethernet 0
3AXD50001109462 — Environmental
ParameterValue
Temperature rating, max.Maximum 40 °C
3AXD50001109462 — Mechanical
ParameterValue
Degree of protection (IP)IP66
Enclosure type (NEMA)Type4X
Mounting typeWall-mounted

Product details

The ABB 3AXD50001109462 is a wall-mounted drive rated for 5.5 kW normal-use output at 24.5 A from a 200-240 V three-phase supply. It ships with the control unit included and carries IP66 / NEMA 4X protection. Heavy-duty cycle rating is 4 kW at 16.7 A; light-overload matches the normal-use figure at 24.2 A. UL listing shows 7.5 Hp at 24 A for the light-overload case.

The 0.98 power factor and IE2 efficiency class tell you this drive draws near-unity from the line at rated load — no power-factor correction caps needed upstream. Standby loss of 14 W is the heat it dumps into a panel or wall space when the motor is stopped; factor that into your ventilation calculation if the drive is in a sealed NEMA 4X cabinet. Maximum ambient is 40 °C. Apparent power rating is 9.8 kV·A. Built-in I/O: 2 analog inputs, 2 analog outputs, 6 digital inputs, and 3 digital outputs.

This drive has IP66 / NEMA 4X enclosure and wall-mount format for pump stations and treatment plants. The included control unit arrives as a single line item.

Frequently asked questions

What does the 'Includes Control unit' mean?

The drive ships with the control unit integrated — you do not need to order a separate control panel or keypad as an add-on. It is ready for commissioning out of the box.

What are the key output ratings?

Normal-use output is 5.5 kW at 24.5 A; heavy-duty is 4 kW at 16.7 A; light-overload is 5.5 kW at 24.2 A. UL light-overload rating is 7.5 Hp at 24 A.

What enclosure protection does this drive have?

IP66 and NEMA Type 4X, suitable for washdown and outdoor installation without an additional enclosure.

What communication protocol does it use?

CAN-based communication. There is no Industrial Ethernet interface on this variant.

MPN
3AXD50001109462