Skip to main content
ABB 3AXD50001109646 — AC Drive (VFD) 240V

3AXD50001109646 ACH580-01 HVAC Drive, 1.5 kW, 7.6 A, IP66

MPN3AXD50001109646
Active

ABB ACH580-01 series, LV AC wall-mounted HVAC drive, 3AXD50001109646, 1.5 kW / 2 Hp, 7.6 A, 200-240 V, IP66/NEMA 4X, BACnet, IE2.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3AXD50001109646 — Electrical Output
ParameterValue
Output power, normal duty (Pn)1.5 kW
Output current, normal duty (In)7.6 A
Output power, heavy duty (PhD)1.1 kW
Output current, heavy duty (IhD)6.6 A
Output power, light-overload duty (PlD)1.5 kW
Output current, light-overload duty (IlD)7.5 A
Apparent power output3.0 kV·A
Output power, light-overload duty (UL, Hp)2 Hp
Efficiency class (IE)IE2
Output current, light-overload duty (UL)7.5 A
Standby loss13 W
3AXD50001109646 — Electrical Input
ParameterValue
Input voltage range200 ... 240 V
Number of phases3-phase
Frequency47.5 ... 63 Hz
Power factor0.98
3AXD50001109646 — Control & I/O
ParameterValue
Digital inputs / outputs6 / 3
Communication protocolBACNET
Analog inputs2
Analog outputs2
Hardware interfacesIndustrial Ethernet 0
3AXD50001109646 — Environmental
ParameterValue
Temperature rating, max.Maximum 40 °C
3AXD50001109646 — Mechanical
ParameterValue
Degree of protection (IP)IP66
Enclosure type (NEMA)Type4X
Mounting typeWall-mounted

Product details

The ABB 3AXD50001109646 is an ACH580-01 wall-mounted HVAC drive rated 1.5 kW normal-use (Pn) at 7.6 A on a 200-240 V three-phase supply. Heavy-duty output is 1.1 kW at 6.6 A; light-overload UL listing is 2 Hp at 7.5 A. The drive includes the control unit, two analog inputs and two analog outputs, plus 6 digital inputs and 3 digital outputs. BACnet is the onboard communication protocol — no option card needed for BAS integration. Enclosure is IP66 / NEMA 4X, so it can mount directly on the wall in washdown or outdoor locations without a separate cabinet.

The 0.98 power factor is typical for a modern active-front-end drive — no need for external power-factor correction on the line side. Standby loss of 13 W matters for energy codes that penalize idle draw; this drive meets that threshold for most HVAC schedules. Maximum ambient is 40 °C; if the drive is in a hot mechanical room or direct sun, derate output current or add ventilation.

Integration notes

Wall-mounted means the drive has integral mounting tabs and a gland plate for cable entry — no backplate or sub-panel needed. The IP66 / NEMA 4X rating allows hose-down cleaning, so it suits food-processing or car-wash HVAC loops. The BACnet MS/TP port is standard; no gateway required to talk to a building controller. The lithium coin cell (CR2032, 220 mAh) keeps the real-time clock and parameter backup; replace it during commissioning if the drive has been in storage over a year.

Frequently asked questions

What are the key output ratings for this drive?

Normal-use output is 1.5 kW at 7.6 A; heavy-duty output is 1.1 kW at 6.6 A; light-overload UL rating is 2 Hp at 7.5 A. Input is 200-240 V three-phase.

What enclosure protection does this drive have?

IP66 / NEMA 4X, suitable for outdoor or washdown installation without a separate cabinet.

What communication protocol is built in?

BACnet MS/TP is the onboard protocol. No option card is required for building automation system integration.

Does the drive include the control unit?

Yes, the control unit is included in the order code.

MPN