What this drive is, in plain terms
The ACS510-01-180A-4 sits in the ABB Standard Drives family on the R6 frame size, rated 180 A nominal continuous output and 9 kW continuous. It ships as a standard low-voltage AC drive intended for industrial motor control, with the braking and output-filter components already specified into the build.
Continuous and peak sizing
The continuous rating is 9 kW at 180 A nominal output current — that's the figure a panel designer uses to match the drive to the motor nameplate for steady-state load. Peak braking reaches 135 kW into a SAFUR125F500 brake resistor selected at 4 Ohm through the NBRA-657C chopper — the peak figure is what governs stop performance on high-inertia or overhauling loads, not the continuous kW.
Output filter and motor cable reach
The factory output choke is FOCH-0260-70, rated for 289 A thermal current, which lets the motor cable run out to 300 m whether the choke is fitted or not. Long cable runs on an AC drive are the classic source of reflected-wave and EMC trouble, so the choke pair matters more in a retrofit or a distributed panel than in a wall-mounted drive inches from the motor.