Skip to main content
ABB ACS800-04-0260-3+E210+0N664 — AC Drive (VFD) 480V

ABB ACS800-04-0260-3+E210+0N664 drive, 160 kW HD, R8

MPNACS800-04-0260-3+E210+0N664
End of Life

ABB ACS800-04-0260-3+E210+0N664 single drive module, 380–415 V three-phase, 200 kW light-overload and 160 kW heavy-duty, R8 frame, 206 kg.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

ACS800-04-0260-3+E210+0N664 — Input / Supply
ParameterValue
Input voltage range380 ... 415 V
Number of phases3
Frequency48 ... 63 Hz
ACS800-04-0260-3+E210+0N664 — Mechanical & Cooling
ParameterValue
Frame sizeR8
Mounting typeModule for cabinet assembly
ACS800-04-0260-3+E210+0N664 — Other specifications
ParameterValue
Weight206 Kg
Product typeSingle drive module
Output current, normal use445 A
Output power, Heavy-Duty use160 kW
Output current, heavy- duty use340 A
Output power, Light-Overload use200 kW
Output current, light- overload use440 A

Product details

The ABB ACS800-04-0260-3+E210+0N664 is a single drive module in the ACS800-04 family, built as a module for cabinet assembly rather than a stand-alone or wall-mount package. Input is three-phase 380–415 V at 48–63 Hz, so the upstream feed and any line reactor or filter sizing has to be worked against that envelope.

Read the two duty numbers, not the headline

Output current for normal use is 445 A, but the figure that actually governs motor sizing is the heavy-duty rating: 160 kW at 340 A. Light-overload use runs 200 kW at 440 A.

Where the part fits in a panel

The cabinet-assembly form factor means the drive goes inside an enclosure with the line reactor, fuses or breaker, and cable terminations all worked out around the R8 footprint; cooling airflow and clearance above and below the module follow the cabinet-assembly manual, not a chassis-mount note.

Second-source check, not a swap

A panel originally specified around ACS800-104-0440-7 will not accept the ACS800-04-0260-3 without rework on the input voltage class, the cabinet cut-out, and the cooling arrangement; treat them as different products, not alternates.

Frequently asked questions

What is the heavy-duty rating on the ACS800-04-0260-3+E210+0N664?

Heavy-duty use is 160 kW at 340 A; light-overload use is 200 kW at 440 A. For hard-start motor loads, the 160 kW / 340 A figure is the one that governs sizing.

Is the ACS800-04-0260-3+E210+0N664 a wall-mount or cabinet module?

It is a module for cabinet assembly, not a wall-mount or stand-alone drive. The R8 frame and 206 kg mass set the cabinet footprint, cooling clearances, and rigging plan.

What input supply does the ACS800-04-0260-3+E210+0N664 need?

Three-phase 380–415 V at 48–63 Hz. Upstream protection and any line reactor or EMC filter are sized against that envelope.

How long is the lead time on the ACS800-04-0260-3+E210+0N664?

Estimated lead time is 28–32 weeks, so a maintenance spare has to be on order well ahead of any planned outage, and a new-installation order has to be placed against the project dock date rather than the energisation date.

MPN