Wall-mount form factor and panel fit
The ACS880-01-02A4-3: The NEMA Type 1 enclosure with IP21 protection means it's suited for indoor, dry locations where falling dirt and dripping water are not a concern. No knockouts for conduit entry are pre-cut — plan for cable glands or a separate junction box above the drive.
Input power and ambient limits
Rated for 380-415 V AC, 3-phase input at 47.5-63 Hz, which covers standard 50 Hz and 60 Hz industrial supplies worldwide. The 40 °C maximum ambient temperature is the baseline for full rated output — above that, output current must be derated per the drive's thermal curve. Altitude rating to 4000 m means the drive can be installed at high-elevation sites without pressure-related derating, though above 1000 m the air density drop may require additional current derating for the same thermal margin.
Control I/O and standby losses
The drive carries 2 analog inputs, 2 analog outputs, 6 digital inputs, and 2 digital outputs — enough for basic speed reference, feedback, and run/stop control without an external I/O expansion module for most pump, fan, and conveyor applications. Standby loss of 23 W is low enough that the drive can remain powered in a sealed panel without active cooling, as long as the total panel heat load stays within the enclosure's dissipation rating.