Skip to main content
ABB AF80-30-00-11 — Contactors

ABB AF80-30-00-11 Contactor, 105 A, 1000 VAC, 20-60 VDC Coil

MPNAF80-30-00-11

ABB AF80 series, 3-pole contactor, 105 A, 1000 VAC, 20-60 VDC coil, surface mount.

$349.59Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

AF80-30-00-11 — Specifications
ParameterValue
Amps105
TypeContactor
Poles3
MountingSurface
Volts AC1000
Volts DC control20-60

Product details

Rating and fit

The ABB AF80-30-00-11 is a 3-pole contactor rated for 105 A at 1000 VAC, with a 20-60 VDC control coil. The 105 A rating is the continuous thermal current (Ith) — the current the main poles can carry continuously in an enclosed panel without exceeding the temperature rise limits. Surface-mount design means it bolts directly to a backplate or panel — no DIN rail adapter. Plan for M6 or M8 mounting hardware and sufficient clearance for the arc chutes above and below. The coil draws from a 20-60 VDC supply; at 24 VDC nominal the pickup voltage is around 18 V, dropout below 10 V. If your control voltage is 24 VDC, the AF80-30-00-11 holds cleanly; if you're on a 48 VDC bus, it sits in the middle of the coil range without a dropping resistor.

Coil voltage range

The 20-60 VDC control coil is a wide-band coil — it covers nominal 24 V, 36 V, and 48 VDC systems without needing a coil change. That's useful if your panel has mixed DC bus voltages or if you're standardizing on one contactor variant across multiple machine builds. The AC coil variant (24-60 V 50/60 Hz) is also available under the same order code prefix; the AF80-30-00-11 specifically is the DC coil version as listed.

Frequently asked questions

How do I get pricing and availability for AF80-30-00-11?

Submit an RFQ through this listing. Pricing and availability are confirmed at quote time through independent distribution channels.

What is the 105 A rating on this contactor?

The 105 A is the continuous thermal current (Ith) for the main poles at 1000 VAC. For motor duty (AC-3), the practical switching current is lower — typically 55-65 A depending on the load and switching frequency.

What control voltage does AF80-30-00-11 use?

The coil accepts 20-60 VDC, covering nominal 24 V, 36 V, and 48 VDC systems without a coil change.

MPN
AF80-30-00-11