The ABB AF80-30-11-41 is a three-pole contactor rated for 80 A, with a coil voltage range of 24-60 V.
What the 80 A rating means for fit
The 80 A rating is the contactor's thermal current (Ith) under AC-1 duty, meaning it handles resistive loads up to that level continuously. For motor starting (AC-3 duty), the actual switching capacity is lower — typically around 37 kW at 400 V for this frame size. The 24-60 V coil gives flexibility across common control voltages in 24 VDC or 48 VAC systems.