It handles 277 VAC and 60 VDC circuits, with a 6 kA interrupting rating on AC and 10 kA on DC. Snaps onto standard DIN rail for panel integration — no special tools needed for a quick swap.
Curve C means the magnetic trip threshold sits at 5–10× rated current (30–60 A for this 6 A unit). It's the standard pick for lighting circuits, general-purpose outlets, and moderate motor starts where you need to ride out the inrush without nuisance tripping.