The ABB S201P-D6 is a 1-pole miniature circuit breaker rated 6 A with a Trip Curve D characteristic, meaning its magnetic trip operates between 10x and 20x In — designed for loads with high inrush currents like small motors, transformers, or solenoid valves where a B or C curve would nuisance-trip on startup.
ABB S201P-D6 MCB 1P D 6A 277V AC, 10 kA Interrupt Rating
ABB S201P-D6 miniature circuit breaker, 1-pole, Trip Curve D, 6 A, 277 V AC, 10 kA interrupting capacity, DIN rail mount.
Specifications
| Parameter | Value |
|---|---|
| Amps | 6 |
| Type | Trip Curve D |
| Poles | 1 |
| Mounting | DIN Rail |
| Volts AC | 277 |
| Breaking capacity | 10 kA |
Product details
Frequently asked questions
What is S201P-D6's listed amps and trip curve?
The S201P-D6 is rated 6 A with Trip Curve D (magnetic trip 10x–20x In), 1-pole, 277 V AC, 10 kA interrupting capacity.
Where can I buy S201P-D6?
Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.
Will S201P-D6 drop into a panel specified around S201MUC-K2 without rewiring?
Both are 1-pole DIN-rail MCBs with the same 277 V AC rating, but the S201P-D6 uses Trip Curve D (10x–20x In) while the S201MUC-K2 uses Trip Curve K (8x–12x In magnetic, plus thermal). The S201P-D6 also carries a higher 10 kA AC interrupting rating versus the S201MUC-K2's 6 kA AC. Physically they share the same footprint and mounting, so a swap is mechanically possible, but the trip curve difference means the S201P-D6 allows higher inrush before magnetic trip — verify coordination with downstream loads before substituting.