Skip to main content
ABB S202-Z6 — 2-Pole MCB (DIN Rail)

ABB S202-Z6 MCB 2P Z 6A 277V, Trip Curve Z

MPNS202-Z6

ABB S202-Z6, 2-pole miniature circuit breaker, 6 A, Trip Curve Z, 277 VAC, 6 kA interrupting rating, DIN rail mount.

$17.78Ref. price · indicative, final on quote
StockContact for availability
Lead timeCall for availability wk
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Specifications

S202-Z6 — Specifications
ParameterValue
Amps6
TypeTrip Curve Z
Poles2
MountingDIN Rail
Volts AC277
Breaking capacity6 kA

Product details

What the ratings mean for fit

The ABB S202-Z6 is a 2-pole miniature circuit breaker rated 6 A with a Trip Curve Z characteristic, designed for DIN-rail mounting in distribution panels and control cabinets. The 6 A rating sets the continuous current it can carry without tripping under normal conditions. Trip Curve Z means the magnetic trip operates between 2 and 3 times the rated current — faster than Curve B or C — making it the right choice for protecting semiconductor circuits, control transformers, and other sensitive electronic loads where a standard MCB would allow too much fault energy through before clearing. Rated 277 VAC phase-to-neutral (480Y/277 V wye systems), it fits directly into North American 277/480 V lighting and control panels. The 6 kA interrupting rating at 277 VAC means it can safely clear a fault up to that level without welding contacts or rupturing the case — adequate for most secondary distribution panels where the available fault current stays under 6 kA.

Panel integration notes

Snaps onto standard 35 mm DIN rail per EN 60715. The 2-pole width occupies two modular spaces (36 mm), leaving room alongside other S200-series breakers for a clean, ganged appearance. Wire termination accepts up to 25 mm² conductor; torque to the nameplate value for reliable contact over the breaker's service life.

Frequently asked questions

Where can I buy S202-Z6 and how do I get a price?

The S202-Z6 is sourced to order against an RFQ through independent distribution. Submit an RFQ for current availability and pricing confirmed at quote time.

What is S202-Z6's listed amps and trip curve type?

The S202-Z6 is rated 6 A with a Trip Curve Z characteristic — magnetic trip between 2x and 3x rated current for sensitive electronic load protection.

Will S202-Z6 drop into a panel specified around S203-C8 without rewiring?

No — the S203-C8 is a 3-pole breaker rated 8 A with Trip Curve C. The S202-Z6 is 2-pole, 6 A, Curve Z. It will not directly replace a 3-pole breaker without reconfiguring the circuit and enclosure space.

MPN
S202-Z6