Skip to main content
ABB S202MUC-Z16 — 2-Pole MCB (DIN Rail)

ABB S202MUC-Z16 MCB 2P Z-Curve 1.6 A DIN Rail

MPNS202MUC-Z16

ABB S200MUC series, S202MUC-Z16, 2-pole Z-curve MCB, 1.6 A, 277 VAC / 500 VDC, 6 kA AC / 10 kA DC interrupting rating, DIN rail mount.

$177.88Ref. price · indicative, final on quote
StockContact for availability
Lead timeCall for availability wk
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Specifications

S202MUC-Z16 — Specifications
ParameterValue
Amps1.600
TypeTrip Curve Z
Poles2
MountingDIN Rail
Volts AC277
Volts DC500
Breaking capacity6 kA
Interrupt rating DC10 kA

Product details

What the ratings mean for fit

The ABB S202MUC-Z16 is a 2-pole miniature circuit breaker from the S200MUC series, rated 1.6 A with a Z trip curve. That 1.6 A rating is the continuous current it carries without tripping — undersized for a motor branch, but spot-on for protecting a control transformer secondary, a PLC power supply feed, or a 24 VDC sensor loop where you want tight overcurrent protection. The Z curve means it trips between 2x and 3x rated current (3.2 A to 4.8 A), which is faster than a C curve and avoids nuisance trips on moderate inrush from small inductive loads like contactor coils or relay banks. Mounts on standard DIN rail, so it clips into any panel enclosure.

Interrupting capacity and voltage range

Rated 277 VAC with a 6 kA interrupting capacity — that covers most single-phase control circuits fed from a 277/480 V panel. On the DC side it handles 500 VDC at 10 kA, which is useful for battery banks or DC bus protection in drives. The 500 VDC rating is higher than typical 60 V or 125 V DC breakers in this form factor, so it's a candidate for string-level solar combiner boxes or UPS output circuits. The 10 kA DC interrupt is the figure that matters for fault-clearing in those applications.

Frequently asked questions

What does the Z trip curve mean on this breaker?

The Z curve trips between 2x and 3x rated current (3.2 A to 4.8 A), making it faster than a C curve and suited for protecting sensitive electronic loads like PLC power supplies or control transformers where you want tight overcurrent protection without nuisance trips on moderate inrush.

What is the interrupting rating of the S202MUC-Z16?

6 kA at 277 VAC and 10 kA at 500 VDC — the DC rating is notably high for a breaker this size, covering battery banks and solar combiner applications.

Where can I buy the S202MUC-Z16?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing confirmed at quote time.

Will the S202MUC-Z16 fit in a panel designed for a single-pole breaker like the S201M-C3?

No — the S202MUC-Z16 is a 2-pole breaker requiring two DIN-rail module widths, while the S201M-C3 is 1-pole and occupies one module. You can't drop it into the same slot without panel rework.

MPN