ABB S203P-Z40 — 3-Pole MCB (DIN Rail)

ABB S203P-Z40 MCB, 3P, 40A, Curve Z, 10kA, DIN Rail

MPNS203P-Z40

ABB S203P-Z40, 3-pole miniature circuit breaker, 40 A, Trip Curve Z, 277 VAC, 10 kA interrupting rating, DIN rail mount.

$59.69Ref. price · indicative, final on quote
StockContact for availability
Lead timeCall for availability wk
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

S203P-Z40 — Identification
ParameterValue
Number of poles3

Electrical

S203P-Z40 — Electrical
ParameterValue
Voltage (AC)277
Current (A)40

Protection

S203P-Z40 — Protection
ParameterValue
Interrupting rating (AC)10 kA

Mechanical

S203P-Z40 — Mechanical
ParameterValue
Mounting typeDIN Rail

Other specifications

S203P-Z40 — Other specifications
ParameterValue
TypeTrip Curve Z

Product details

What this MCB is and what the ratings mean

The ABB S203P-Z40 is a 3-pole miniature circuit breaker rated 40 A with a Trip Curve Z characteristic, designed for DIN-rail mounting in distribution panels. The 40 A rating means it carries continuous loads up to that current without tripping, and the 10 kA interrupting rating at 277 VAC tells you it can safely clear a fault up to that level — enough for most commercial and light industrial service-entrance or sub-feed applications. Curve Z is the tightest standard trip curve, tripping between 2 and 3 times rated current (80–120 A for this unit), which makes it the right choice for protecting semiconductor circuits, PLC power supplies, and other sensitive electronic loads where a standard C-curve would let through too much energy before opening.

Where it fits in the panel

Snaps onto standard 35 mm DIN rail, same footprint as the rest of the S200 series. Three poles means it switches all phases simultaneously — required for three-phase sub-feeds or motor branch circuits where you need full disconnection. The 277 VAC phase-to-neutral rating matches 480Y/277 V wye systems, so it's a direct fit for North American commercial panels fed from a 480/277 V transformer.

Frequently asked questions

How do I get current pricing and availability for S203P-Z40?

Submit an RFQ through this listing. We source it to order and confirm availability and pricing at quote time.

What's the difference between S203P-Z40 and S203-D13?

The S203-D13 is a 10 A, Curve D breaker — same 3-pole DIN-rail footprint and 10 kA interrupt rating, but the trip curve is much slower (10–20× rated current). The Z40 is for sensitive electronic loads; the D13 is for motor or transformer inrush. They share the same physical dimensions and busbar pattern, so swapping one for the other on the same panel requires no rewiring — just verify the ampacity and trip coordination match the circuit.

What is S203P-Z40's listed amps?

40 A continuous rating.

What does Trip Curve Z mean?

Curve Z trips at 2 to 3 times rated current — for the 40 A unit, that's 80–120 A magnetic trip. It's the fastest standard curve, designed to protect semiconductor circuits and sensitive electronics where a C-curve would pass too much fault energy.

Will S203P-Z40 drop into a panel specified around S203-D13 without rewiring?

Yes — same 3-pole DIN-rail footprint, same busbar spacing. The swap is mechanical; just verify the 40 A rating and Curve Z trip characteristic match the circuit protection requirements.