Specification and fit
Interrupt rating is 50 kA at 230 VAC. Trip Curve C provides magnetic trip between 5 and 10 times rated current (80–160 A for this 16 A unit), making it the standard choice for protecting general-purpose loads like lighting circuits, socket outlets, and control transformers where moderate inrush is expected.
Integration note
Snap-on DIN rail mounting per EN 60715 — installs into any standard 35 mm rail in the panel, with the busbar comb bridging across the 2-pole footprint.