Skip to main content
ABB XT1NQ3030AAA000XXX — Molded Case Circuit Breakers (MCCB)

ABB XT1NQ3030AAA000XXX MCCB, 30A 3P 480V, 18kAIC

MPNXT1NQ3030AAA000XXX

ABB Tmax XT1N, Molded Case Circuit Breaker, 30A, 3-Pole, 600Y/347VAC, 18kAIC, Thermal-Magnetic Fixed Trip, UL 100% Rated, Panel Mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

XT1NQ3030AAA000XXX — Specifications
ParameterValue
Amps30
Poles3
MountingPanel
Volts AC480

Product details

30 A thermal-magnetic fixed trip in the Tmax XT1N frame

The ABB XT1NQ3030AAA000XXX is a 30 A, 3-pole molded case circuit breaker in the Tmax XT1N 125 A frame, with a fixed thermal-magnetic trip unit. The 30 A rating means it protects a circuit whose continuous load stays at or below 30 A — sized for a 30 A feeder or a motor branch circuit where the full-load current lands under that mark. The fixed trip eliminates adjustment points, so what you spec is what you get; no field-calibration drift. Rated 600Y/347 VAC with an interrupting capacity of 18 kAIC, this MCCB handles fault currents up to 18 kA at that voltage without losing its integrity. The 480 VAC line-to-line rating covers common North American 480Y/277 V wye systems. The UL 100% rating means it can carry its full 30 A continuously without derating — a real advantage in a packed panel where ambient heat builds.

Panel-mount integration and frame notes

Panel-mounted, not DIN-rail — the XT1N frame bolts into a cutout or mounts on a backplate. The fixed front flat terminals accept standard lug or bus-bar connections; torque them to the manufacturer's spec for the 30 A path. The 125 A frame size gives mechanical headroom: the same physical breaker can be ordered with higher trip ratings, so the mounting footprint stays consistent across a panel's MCCB lineup.

Frequently asked questions

What is the interrupting rating of this MCCB?

18 kAIC at 600Y/347 VAC. That covers most industrial secondary-distribution fault levels; for higher available fault current, step up to the XT1N frame's 25 kAIC variant or move to the XT2 frame.

Where can I buy the XT1NQ3030AAA000XXX?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing confirmed at quote time — submit an RFQ for a firm price and lead time.

What compliance documentation does ABB provide for this breaker?

UL 489 listed (the UL 100% rated mark), CSA C22.2 No. 5, and CE-marked for IEC markets. RoHS and REACH declarations are available through ABB's document portal.

MPN
XT1NQ3030AAA000XXX