70 A MCCB with 35 kA interrupting capacity
The ABB XT1SU3070AFF000XXX is a 3-pole molded case circuit breaker from the XT1S 125 series, rated 70 A continuous at 480 VAC. Panel-mount construction suits enclosure-based distribution, not DIN-rail assembly.
The 70 A thermal-magnetic trip unit (TMF 70-700) provides fixed thermal and magnetic settings. For selective coordination downstream, verify that the instantaneous pickup of this breaker clears faults before the upstream device trips — the 35 kA SCCR gives headroom for most industrial panels. The 3-pole construction covers three-phase loads; the neutral is not switched.
Panel integration
Panel-mount design requires a cutout and four mounting screws — no DIN rail adapter. The XT1S 125 frame accepts plug-in accessories (auxiliary contacts, shunt trip, undervoltage release) that snap into the front accessory slot without removing the breaker. Torque terminals to the manufacturer's specification; the line and load lugs accept copper or aluminum conductors.