Skip to main content
ABB 1SDA068114R1

ABB 1SDA068114R1 XT4N MCCB, 20 A, 3-pole, MA trip, 690 V

MPN 1SDA068114R1

ABB 1SDA068114R1 XT4N 160 MCCB, MA magnetic-only trip unit, In 20 A, Iu 160 A, 3-pole, 690 V, 50/60 Hz, DIN rail.

$433.00 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

1SDA068114R1 specifications
ParameterValue
Product typeXT4N 160 MA 20 Im=100...200 3p F F
Voltage690 V
Current20 A
Frequency50/60 Hz
Poles3 poles
Weight2.1 Kg
DimensionsXT4

Product details

Motor branch circuit protection with an MA trip

The 1SDA068114R1 is an ABB SACE Tmax XT4N 160 frame MCCB with a magnetic-only (MA) trip unit set at In=20 A. The MA trip responds only to short-circuit and high overcurrents — it has no thermal element, so motor overload protection must be provided by a separate overload relay in the branch circuit. The frame rating Iu=160 A means the breaker's internal bus and contacts are sized for 160 A continuous, but the trip threshold is set by the installed MA module to 20 A. This lets the same frame cover a wide range of motor FLA settings by swapping the trip unit.

MPN
1SDA068114R1