Skip to main content
ABB S202MUC-K63

ABB S202MUC-K63 S200MUC 2P K 63 A MCB, DIN Rail

MPN S202MUC-K63

ABB S200MUC series, MCB, 2-pole, 63 A, Trip Curve K, 277 VAC / 500 VDC, 6 kA AC / 10 kA DC interrupting capacity, DIN-rail mount.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

S202MUC-K63 specifications
ParameterValue
Product typeTrip Curve K
Voltage500 V
Current63 A
Breaking capacity6 kA
Poles2
MountingDIN Rail

Product details

The ABB S202MUC-K63 is a 2-pole miniature circuit breaker from the S200MUC series, rated at 63 A with a Trip Curve K characteristic. The K curve means the magnetic trip operates between 10× and 14× In (630 A to 882 A peak), which is deliberately set above the inrush of transformers, solenoid valves, and motor starters so the breaker holds through the start transient and only clears a hard fault. On a 277 VAC line-to-neutral or a 500 VDC battery string, the interrupting capacity is 6 kA AC and 10 kA DC respectively — that's the fault current the breaker can safely extinguish without welding contacts or rupturing the housing. The 2-pole configuration lets it switch both phase and neutral on a split-phase circuit, or both poles in a DC system where polarity isolation matters.

MPN
S202MUC-K63