Skip to main content
Siemens 3RT2036-3AP60

Siemens 3RT2036-3AP60 SIRIUS Power Contactor, 52 A at 480 V

MPN 3RT2036-3AP60
Active

Siemens SIRIUS, power contactor, size S2, 3RT2036-3AP60, 52 A at 480 V AC-3, spring-type coil terminals, screw and snap-on 35 mm DIN rail mount.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

3RT2036-3AP60 specifications
ParameterValue
Depth130 mm
Width55 mm
Height114 mm
Arcing time10 ... 20 ms

Product details

The coil terminals use spring-type connections, so you land the control wiring without a screwdriver — a time-saver on the panel build. The main contact block is configured as 18 normally-open and 1 normally-closed, which is a common arrangement for a reversing or star-delta starter where you need the extra NO pole for a holding circuit or a status feedback to the PLC.

Clearance requirements are tight: 10 mm upwards and forwards, 6 mm at the sides, 10 mm downwards. That means you can pack contactors side-by-side without the usual 20 mm gap, which saves rail space in a multi-starter panel.

The 52 A at 480 V AC-3 is the headline number — that's the motor-switching current. For resistive loads (AC-1), the contactor can handle higher currents, but the AC-3 figure is what governs motor duty. Switching frequency limits are given per duty class: 1000 cycles/hour for AC-1 (resistive), 800 for AC-3 (motor start/run), and 250 for AC-4 (plugging/inching). If your application requires frequent reversing or inching, the AC-4 limit of 250 cycles/hour is the binding constraint — don't exceed it or the arc chutes will wear prematurely.

MPN
3RT2036-3AP60