Skip to main content
Siemens 3RV1021-1EA10

Siemens 3RV1021-1EA10 SIRIUS Motor Protection Circuit Breake

MPN 3RV1021-1EA10

Siemens SIRIUS 3RV1021-1EA10 motor protection circuit breaker, 4 A rated continuous current, Class 10 trip, 100 kA breaking capacity at 400 V AC, screw-type terminals, IP20 front face.

$68.00 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

3RV1021-1EA10 specifications
ParameterValue
Depth96 mm
Width45 mm
Height97 mm
Trip classCLASS 10

Product details

It carries a continuous current rating of 4 A and a trip class of CLASS 10, meaning it will trip within 10 seconds at 7.2x the current setting — fast enough to protect standard induction motors during a locked-rotor event without nuisance tripping on normal starts. No ground fault detection on this variant, so pair it with a separate ground-fault relay if that's required by code.

The 45 mm width takes up a single 9 mm module equivalent on the rail — five of these fit in a standard 225 mm wide enclosure row. Screw-type terminals on both main and auxiliary circuits accept solid or stranded wire: 2x (1 … 2.5 mm²) or 2x (2.5 … 6 mm²) per clamp. AWG equivalents are 2x (14 … 10). Finely stranded wire with ferrule is handled the same way — no special tooling needed beyond a standard screwdriver. Mounting position is any orientation. Shock resistance rated at 25g / 11 ms, so it holds up in mobile equipment or near vibrating machinery.

RoHS compliance is indicated by the substance prohibition date of 01.05.2012, which aligns with the EU RoHS directive. No UL or CSA listing is stated in the spec record, so verify jurisdictional acceptance if your project requires those marks.

Power Dissipation and Duty Cycle

That's modest — no forced cooling needed in a standard IP20 enclosure, but account for it in thermal calculations if you're packing multiple units in a small cabinet. Maximum operating frequency in AC-3 duty is 15 operations per hour. That's fine for motor starting in pump or fan applications; don't use it for frequent jogging or reversing cycles without checking the thermal accumulation.

MPN
3RV1021-1EA10